Appendices C Table of Parameters
C - 40
High-function General-purpose Inverter RX2 Series User’s Manual
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial value
Note
bC110
○
Electronic thermal level setting,
1st-motor
(0.0 to 3.0)
× Inverter rated current
*1
*1. On the parameter about the current and the voltage, the figures and the units to be handled vary in the setting path.
1) Operator or CX-Drive: 0.1 A or 0.1 V (When CX-Drive is operated, set [CF-11] Resister data selection to 00 (A,V). When the data of
[CF-11] Resister data selection is not set to 00 (A,V), it is not set or displayed correctly.)
2) Modbus: The current and the voltage vary, depending on the setting of Resister data selection [CF-11].
When [CF-11] Resister data selection is set to 00 (A,V), 0.1 A, 0.1 V
When [CF-11] Resister data selection is set to 01 (%), 0.01% (Rated ratio)
3) Drive programming: 0.01% (Rated ratio)
1.0
× Inverter
rated current
bC111
○
Electronic thermal characteris-
tic selection, 1st-motor
00 (Reduction characteristics)/
01 (Constant torque characteristics)/
02 (Arbitrary setting)
00
*2
*2. It is a default value when Default Value Selection (Ub-02) is set to 01.
bC112
○
Electronic thermal Subtraction
function enable, 1st-motor
00 (Disabled)/01 (Enabled)
01
bC113
○
Electronic thermal Subtraction
time, 1st-motor
1 to 1000 (s)
600
bC-14
○
Electronic thermal counter
memory selection at Power-off
00 (Disabled)/01 (Enabled)
01
bC120
○
Free electronic thermal fre-
quency-1, 1st-motor
0.00 to [bC122] (Hz)
0.00
bC121
○
Free electronic thermal cur-
rent-1, 1st-motor
(0.0 to 3.0)
× Inverter rated current
*1
0.0
bC122
○
Free electronic thermal fre-
quency-2, 1st-motor
[bC120] to [bC124] (Hz)
0.00
bC123
○
Free electronic thermal cur-
rent-2, 1st-motor
(0.0 to 3.0)
× Inverter rated current
*1
0.0
bC124
○
Free electronic thermal fre-
quency-3, 1st-motor
[bC122] to 590.00 (Hz)
0.00
bC125
○
Free electronic thermal cur-
rent-3, 1st-motor
(0.0 to 3.0)
× Inverter rated current
*1
0.0
bC210
○
Electronic thermal level setting,
2nd-motor
(0.0 to 3.0)
× Inverter rated current
*1
1.0
× Inverter
rated current
bC211
○
Electronic thermal characteris-
tic selection, 2nd-motor
00 (Reduction characteristics)/
01 (Constant torque characteristics)/
02 (Arbitrary setting)
01
*2
bC212
○
Electronic thermal Subtraction
function enable, 2nd-motor
00 (Disabled)/01 (Enabled)
01
bC213
○
Electronic thermal Subtraction
time, 2nd-motor
1 to 1000 (s)
600
bC220
○
Free electronic thermal fre-
quency-1, 2nd-motor
0.00 to [bC222] (Hz)
0.00
bC221
○
Free electronic thermal cur-
rent-1, 2nd-motor
(0.0 to 3.0)
× Inverter rated current
*1
0.0
bC222
○
Free electronic thermal fre-
quency-2, 2nd-motor
[bC220] to [bC224] (Hz)
0.00
bC223
○
Free electronic thermal cur-
rent-2, 2nd-motor
(0.0 to 3.0)
× Inverter rated current
*1
0.0
bC224
○
Free electronic thermal fre-
quency-3, 2nd-motor
[bC222] to 590.00 (Hz)
0.00
bC225
○
Free electronic thermal cur-
rent-3, 2nd-motor
(0.0 to 3.0)
× Inverter rated current
*1
0.0
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...