Appendices C Table of Parameters
C - 54
High-function General-purpose Inverter RX2 Series User’s Manual
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial value
Note
CE101
○
Low current signal output mode
selection, 1st motor
00 (During acceleration/deceleration, at constant
speed)/
01 (Only at constant speed)
01
CE102
○
Low current detection level 1,
1st motor
(0.0 to 2.0)
× Inverter rated current
*1
1.0
× Inverter rated
current
CE103
○
Low current detection level 2,
1st motor
(0.0 to 2.0)
× Inverter rated current
*1
1.0
× Inverter rated
current
CE105
○
Over current signal output mode
selection, 1st motor
00 (During acceleration/deceleration, at constant
speed)/
01 (Only at constant speed)
01
CE106
○
Over current detection level 1,
1st motor
(0.0 to 2.0)
× Inverter rated current
*1
1.0
× Inverter rated
current
CE107
○
Over current detection level 2,
1st motor
(0.0 to 2.0)
× Inverter rated current
*1
1.0
× Inverter rated
current
CE-10
○
Arrival frequency setting during
acceleration 1
0.00 to 590.00 (Hz)
0.00
CE-11
○
Arrival frequency setting during
deceleration 1
0.00 to 590.00 (Hz)
0.00
CE-12
○
Arrival frequency setting during
acceleration 2
0.00 to 590.00 (Hz)
0.00
CE-13
○
Arrival frequency setting during
deceleration 2
0.00 to 590.00 (Hz)
0.00
CE120
○
Over torque level (Forward driv-
ing), 1st motor
0.0 to 500.0 (%)
100.0
CE121
○
Over torque level (Reverse
regenerative), 1st motor
0.0 to 500.0 (%)
100.0
CE122
○
Over torque level (Reverse driv-
ing), 1st motor
0.0 to 500.0 (%)
100.0
CE123
○
Over torque level (Forward
regenerative), 1st motor
0.0 to 500.0 (%)
100.0
CE-30
○
Electronic thermal warning level
(MTR)
0.00 to 100.00 (%)
80.00
CE-31
○
Electronic thermal warning level
(CTL)
0.00 to 100.00 (%)
80.00
CE-33
○
Zero speed detection level
0.00 to 100.00 (%)
0.50
CE-34
○
Cooling FAN over-heat warning
level
0 to 200 (°C)
120
CE-36
○
Accum.RUN(RNT)/Accum.Pow
er-on (ONT) time setting
0 to 100000 (hr)
0
CE-40
○
Window comparator for [Ai1]
higher level
0 to 100 (%)
100
CE-41
○
Window comparator for [Ai1]
lower level
0 to 100 (%)
0
CE-42
○
Window comparator for [Ai1]
hysteresis width
0 to 10 (%)
0
CE-43
○
Window comparator for [Ai2]
higher level
0 to 100 (%)
100
CE-44
○
Window comparator for [Ai2]
lower level
0 to 100 (%)
0
CE-45
○
Window comparator for [Ai2]
hysteresis width
0 to 10 (%)
0
CE-46
○
Window comparator for [Ai3]
higher level
-100 to 100 (%)
100
CE-47
○
Window comparator for [Ai3]
lower level
-100 to 100 (%)
-100
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......