C - 57
Appendices C Table of Parameters
High-function General-purpose Inverter RX2 Series User’s Manual
C-
3 Paramet
er List
C
Parameter Mode (Code H)
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial
value
Note
HA-01
-
Auto-tuning selection
00 (Disabled)/01 (Non-rotation)/
02 (Rotation)/03 (IVMS)
00
HA-02
-
RUN command selection at Auto-tuning
00 (RUN key on the LCD operator)/
01 ([AA111]/[AA211])
00
HA-03
-
Online auto-tuning selection
00 (Disabled)/01 (Enabled)
00
HA110
○
Stabilization constant, 1st-motor
0 to 1000 (%)
100
HA115
○
Speed response for Async.M, 1st-motor
0 to 1000 (%)
100
HA120
○
ASR gain switching mode selection,
1st-motor
00 ([CAS] terminal)/
01 (setting switch)
00
HA121
○
ASR gain switching time setting, 1st-motor 0 to 10000 (ms)
100
HA122
○
ASR gain mapping intermediate speed 1,
1st-motor
0.00 to 590.00 (Hz)
0.00
HA123
○
ASR gain mapping intermediate speed 2,
1st-motor
0.00 to 590.00 (Hz)
0.00
HA124
○
ASR gain mapping Maximum speed,
1st-motor
0.00 to 590.00 (Hz)
0.00
HA125
○
ASR gain mapping P-gain 1, 1st-motor
0.0 to 1000.0 (%)
100.0
HA126
○
ASR gain mapping I-gain 1, 1st-motor
0.0 to 1000.0 (%)
100.0
HA127
○
ASR gain mapping P-gain 1 at P-control,
1st-motor
0.0 to 1000.0 (%)
100.0
HA128
○
ASR gain mapping P-gain 2, 1st-motor
0.0 to 1000.0 (%)
100.0
HA129
○
ASR gain mapping I-gain 2, 1st-motor
0.0 to 1000.0 (%)
100.0
HA130
○
ASR gain mapping P-gain 2 at P-control,
1st-motor
0.0 to 1000.0 (%)
100.0
HA131
○
ASR gain mapping P-gain 3, 1st-motor
0.0 to 1000.0 (%)
100.0
HA132
○
ASR gain mapping I-gain 3, 1st-motor
0.0 to 1000.0 (%)
100.0
HA133
○
ASR gain mapping P-gain 4, 1st-motor
0.0 to 1000.0 (%)
100.0
HA134
○
ASR gain mapping I-gain 4, 1st-motor
0.0 to 1000.0 (%)
100.0
HA210
○
Stabilization constant, 2nd-motor
0 to 1000 (%)
100
HA215
○
Speed response for Async.M, 2nd-motor
0 to 1000 (%)
100
HA220
○
ASR gain switching mode selection,
2nd-motor
00 ([CAS] terminal)/
01 (setting switch)
00
HA221
○
ASR gain switching time setting,
2nd-motor
0 to 10000 (ms)
100
HA222
○
ASR gain mapping intermediate speed 1,
2nd-motor
0.00 to 590.00 (Hz)
0.00
HA223
○
ASR gain mapping intermediate speed 2,
2nd-motor
0.00 to 590.00 (Hz)
0.00
HA224
○
ASR gain mapping Maximum speed,
2nd-motor
0.00 to 590.00 (Hz)
0.00
HA225
○
ASR gain mapping P-gain 1, 2nd-motor
0.0 to 1000.0 (%)
100.0
HA226
○
ASR gain mapping I-gain 1, 2nd-motor
0.0 to 1000.0 (%)
100.0
HA227
○
ASR gain mapping P-gain 1 at P-control,
2nd-motor
0.0 to 1000.0 (%)
100.0
HA228
○
ASR gain mapping P-gain 2, 2nd-motor
0.0 to 1000.0 (%)
100.0
HA229
○
ASR gain mapping I-gain 2, 2nd-motor
0.0 to 1000.0 (%)
100.0
HA230
○
ASR gain mapping P-gain 2 at P-control,
2nd-motor
0.0 to 1000.0 (%)
100.0
HA231
○
ASR gain mapping P-gain 3, 2nd-motor
0.0 to 1000.0 (%)
100.0
HA232
○
ASR gain mapping I-gain 3, 2nd-motor
0.0 to 1000.0 (%)
100.0
HA233
○
ASR gain mapping P-gain 4, 2nd-motor
0.0 to 1000.0 (%)
100.0
HA234
○
ASR gain mapping I-gain 4, 2nd-motor
0.0 to 1000.0 (%)
100.0
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......