Appendices C Table of Parameters
C - 62
High-function General-purpose Inverter RX2 Series User’s Manual
Hd203
-
Sync.Motor poles setting, 2nd-motor
2 to 48 (poles)
*1
Hd204
-
Sync.Base frequency setting,
2nd-motor
10.00 to 590.00 (Hz)
*1
Hd205
-
Sync.Maximum frequency setting,
2nd-motor
10.00 to 590.00 (Hz)
*1
Hd206
-
Sync.Motor rated voltage, 2nd-motor
1 to 1000 (V)
*1
Hd208
-
Sync.Motor rated current, 2nd-motor
0.01 to 10000.00 (A)
*1
Hd210
-
Sync.Motor constant R, 2nd-motor
0.000001 to 1000.000000 (Ω)
*1
Hd212
-
Sync.Motor constant Ld, 2nd-motor
0.000001 to 1000.000000 (mH)
*1
Hd214
-
Sync.Motor constant Lq, 2nd-motor
0.000001 to 1000.000000 (mH)
*1
Hd216
-
Sync.Motor constant Ke, 2nd-motor
0.1 to 100000.0 (mVs/rad)
*1
Hd218
-
Sync.Motor constant J, 2nd-motor
0.00001 to 10000.00000 (kgm
2
)
*1
Hd230
○
Minimum Frequency for Sync.M-SLV,
2nd-motor
0 to 50 (%)
8
Hd231
○
No-Load current for Sync.M-SLV,
2nd-motor
0 to 100 (%)
10
Hd232
-
Starting Method for Sync.M, 2nd-motor
00 (Position estimation disabled)/
01 (Position estimation enabled)
00
Hd233
-
IMPE 0V wait number for Sync.M,
2nd-motor
0 to 255
10
Hd234
-
IMPE detect wait number for Sync.M,
2nd-motor
0 to 255
10
Hd235
-
IMPE detect number for Sync.M,
2nd-motor
0 to 255
30
Hd236
-
IMPE voltage gain for Sync.M,
2nd-motor
0 to 200 (%)
100
Hd237
-
IMPE Mg-pole position offset,
2nd-motor
0 to 359 (deg)
0
*1. Varies depending on inverter models and settings of duty rating.
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial
value
Note
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......