8 - 123
8 Applied Settings
High-function General-purpose Inverter RX2 Series User’s Manual
8-
6
A
larm
S
ignal
8
8-6
-1
A
lar
m
Signa
l (
A
L
)
8-6
Alarm Signal
If an overcurrent, overvoltage, or some other error occurs, the inverter shuts off its output and gener-
ates an alarm signal. This is called a “Trip”.
A trip state can be canceled by resetting the inverter, by which the alarm signal also turns OFF.
To reset the inverter, press the STOP/RESET key or input the reset terminal. However, you may not be
able to reset some trip factors by using these methods. In such case, cycle the power supply.
The [AL] function is assigned in the initial state to the contact c relay [CC-07] of AL1-AL0 and AL2-AL0.
You can set the output specifications of contacts a and b to output terminals 11-15, relay output termi-
nals 16A-16C, AL1-AL0, and AL2-AL0 individually.
Precautions for Correct Use
When an inverter outputs error by an interruption of its power supply, in some cases, changes
of wirings and contact selections may alleviate this symptom.
The operations of AL1-AL0 and AL2-AL0 are as follows.
The specifications of the relay contacts AL1-AL0 and AL2-AL0 are as follows.
8-6-1
Alarm Signal (AL)
Alarm Relay AL
[CC-17]
Control power
Inverter error output
Output terminal state
AL1-AL0
AL2-AL0
00
On
Abnormal
Close
Open
Normal
Open
Close
Off
-
Open
Close
01
On
Abnormal
Open
Close
Normal
Close
Open
Off
-
Open
Close
Resistive load
Inductive load
AL1-AL0
Maximum contact capacity
AC250V,2A
DC30V,3A
AC250V,0.2A
DC30V,0.6A
Minimum contact capacity
AC100V,10mA
DC5V,100mA
AL2-AL0
Maximum contact capacity
AC250V,1A
DC30V,1A
AC250V,0.2A
DC30V,0.2A
Minimum contact capacity
AC100V,10mA
DC5V,100mA
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......