8 Applied Settings
8 - 126
High-function General-purpose Inverter RX2 Series User’s Manual
Alarm code is used to output the inverter trip factor as a 3-bit or 4-bit code signal.
Assign the output terminal functions 084 [AC0] to 087 [AC3] alarm code to one of [CC-01] to [CC-07]
that corresponds to the output terminal and output the signal.
Assign 084 [AC0] to 087 [AC3] to the output terminal functions [CC-01] to [CC-07].
The 4-bit output mode is selected when 087 [AC3] is assigned to the output terminal function, whereas
the 3-bit output mode is selected when it is not assigned.
The table below shows the alarm codes to be output.
Precautions for Correct Use
• The output state switches depending on whether 087 [AC3] has been set to [CC-01] to
[CC-07]. The 4-bit output mode is selected when 087 [AC3] has been set, and the signals
084 [AC0], 085 [AC1], 086 [AC2], and 087[AC3] will be output in accordance with the table
below even when all of them have not been set.
• The signals will be output in the 3-bit mode when one of or any pair from 084 [AC0], 085
[AC1], and 086 [AC2] have been set. The signals 084 [AC0], 085 [AC1], and 086 [AC2] will
be output in accordance with the table below even when all of them have not been set.
Parameter
8-6-3
Alarm Code
Item
Parameter
Data
Description
Output terminal func-
tion selection 11-15
[CC-01] to
[CC-05]
084 to 087
084: [AC0] alarm code 0
085: [AC1] alarm code 1
086: [AC2] alarm code 2
087: [AC3] alarm code 3
The signal is output when a trip occurs at the output
terminal assigned.
Relay output terminal
function selection
16A-16C
[CC-06]
Relay output terminal
function selection
AL1-AL0/AL2-AL0
[CC-07]
Alarm Code
Output terminal function
When a 4-bit code is selected
(with [AC3])
When a 3-bit code is selected
(without [AC3])
AC3
AC2
AC1
AC0
Cause
code
Trip description
Cause
code
Trip description
0
0
0
0
Normal
Normal
Normal
Normal
0
0
0
1
E001
Overcurrent error
E001
Overcurrent error
0
0
1
0
E005,E038,
E039
Motor overload error,
low-speed range overload
error, controller overload
error
E005,E038,
E039
Motor overload error,
low-speed range overload
error, controller overload
error
0
0
1
1
E007,E015
Overvoltage, incoming
overvoltage error
E007,E015
Overvoltage, incoming
overvoltage error
0
1
0
0
E009
Undervoltage error
E009
Undervoltage error
0
1
0
1
E016
Momentary interruption
error
E016
Momentary interruption
error
0
1
1
0
E030
IGBT error
E030
IGBT error
0
1
1
1
E006
Braking resistor overload
error
-
Other than above
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......