8 Applied Settings
8 - 154
High-function General-purpose Inverter RX2 Series User’s Manual
8-10 Input Terminal Function
Input terminals 1 to 9, A, and B are open collector inputs. Pulse inputting is possible for Terminals A and
B.
For the content of an input signal, by allocating the functions that you want to operate to [CA-01] to
[CA-11], you will be able to operate the functions with a corresponding input terminal operation.
You can switch a contact for an input signal with the Contacts a/b selection functions of [CA-21] to
[CA-31].
When a function is selected for many targets, the targets will be set to 00 [without allocation], excluding
the finally set function selection.
Parameter
Terminals corresponding to parameters
8-10-1 Overview
Item
Parameter
Data
Description
Input terminal function
selection
[CA-01] to
[CA-11]
Next item: Table
of input terminal
selections
Outputs the allocated function to the corresponding
input terminal.
Selection of Input ter-
minals a/b (NO/NC)
[CA-21] to
[CA-31]
00
Operates as Contact a (NO).
01
Operates as Contact b (NC).
Terminal block
symbol
Function setting destination
parameter
1
[CA-01]
2
[CA-02]
3
[CA-03]
4
[CA-04]
5
[CA-05]
6
[CA-06]
7
[CA-07]
8
[CA-08]
9
[CA-09]
A
[CA-10]
B
[CA-11]
1
[RS]
2
[SCHG]
3
[JG]
4
[FRS]
5
[2CH]
6
[CF1]
7
[CF2]
8
[RV]
9
[FW]
A
[EXT]
B
[USP]
COM
COM
COM
Input terminals
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......