2 - 7
2 Design
High-function General-purpose Inverter RX2 Series User’s Manual
2-1
Installatio
n
2
2-
1-3 I
nstallation
E
n
vironmen
t
Install the inverter in a location that meets the following conditions.
Inverters might be heated up to 150°C and might cause fire accident. Install the inverter on the
non-flammable vertical wall (made of metals and others).
Keep the inverter clear of heating elements such as a braking resistor or reactor so that the heat emit-
ted does not influence the operation.
If the inverter is installed in a control panel, take into consideration dimensions and ventilation to keep
the ambient temperature within the range of the specifications.
To allow heat radiation from inside the inverter, provide the clearance specified in the figure below. Do
not install more than one inverter side by side without clearance.
*1. Save the space for maintenance in the following sites at 22 cm or more. After that, install the inverter.
•
3G3RX2-A2150 to 3G3RX2-A2220
•
3G3RX2-A4150 to 3G3RX2-A4220
The inverter is needed to be taken off when consumable components are replaced on the following models.
•
3G3RX2-A2055 to 3G3RX2-A2110
•
3G3RX2-A4055 to 3G3RX2-A4110
2-1-3
Installation Environment
Operating Environment Conditions
Rating
Operating ambient temperature
*1
*1. The operation of 1,400V-class inverter is only allowed at input voltage below 500 VAC. In case the voltage
exceeds 500 VAC by power supply fluctuation, operate the inverter below 40°C in ambient temperature.
Operating ambient humidity
ND (Normal Duty)
- 10 to 50°C
20% to 90% (with no condensation)
LD (Light Duty)
- 10 to 45°C
20% to 90% (with no condensation)
VLD (Very Light Duty)
- 10 to 40°C
20% to 90% (with no condensation)
Installation Conditions
10 cm min.
30 cm min.
30 cm min.
5 cm min.
5 cm min.
5 cm min.
5 cm min.
3G3RX2-A2004 to 3G3RX2-A2550
3G3RX2-A4007 to 3G3RX2-A4550
3G3RX2-B4750 to 3G3RX2-B413K
Airflow
Wall
Save enough space to prevent the
upper and lower wiring ducts from
blocking cooling airflow.
Inverter
10 cm min.
*1
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......