5 Maintenance and inspection
5-2 Replacing the battery
S8BA-24D24D
□□□
LF
76
5-2-2 Procedure for replacing the battery
For cautions when replacing the battery of the UPS, refer to “Caution for battery
replacement)” shown in the “Safety precautions” of the beginning of this manual.
Notes
Be sure to activate the battery replacement mode before replacing the battery.
▪
For battery replacement, hold down the “Beep Stop/Test” switch on the unit for 10
seconds or longer to activate the battery replacement mode. When the battery
replacement mode is activated, the battery life counter is reset. If the battery life
counter is not reset, a battery deterioration alarm may occur before the expected
life of the battery expires.