background image

S8BA-SBF

36

Before using

The battery has not been charged at the time of purchase. Be sure 
to charge it before use.

Connect this unit to the input power supply to charge the battery 
unit.

When moving the unit from a cold place to a warm place, leave it for 
several hours before using it.

If the unit is promptly turned ON after being moved to a warmer 
place, condensation may form inside the unit and cause it to fail.

Take measures for handling unforeseen accidents, such as data 
backup and system redundancy.

The output may stop when there is failure in this unit.

Connecting

Do not short the unit output lines together, and do not short the battery 
connection cable (to ground).

The unit may fail.

In the event you transfer or sell this unit to a third party, please include 
all of the documentation that came with the unit. This is to ensure that 
the unit is used in line with the conditions described in the included 
documentation.

Using

Before stopping the commercial power to the unit, turn OFF the 
“Power” switch of the unit.
The unit will stop after 30 seconds of setting the mode selection/
backup operation time selection switch to "0.5".

The unit enters Battery Mode when input power supply is stopped.

If the frequency of backup operation becomes high, the battery life 
may be significantly reduced.

Do not use for an application that frequently requires Battery Mode.

The battery unit will deteriorate and fail to maintain the specified 
backup time.

If you want the UPS to stand by in a UPS startup state, set 3 months 
or less for the input power supply stop period.

The UPS startup state means the state of waiting for startup 
triggered by a remote ON/OFF or BS signal.

If the UPS is left unused in the above state for 3 months or longer, 
the battery goes into overdischarge state, and the backup time 
may become shorter or the battery may become unusable.

Storing

Storing the battery in UPS for a long term, store at an environment 
less than 25

°C

 and recharge 15 to 30 minutes the battery within 1 

year.

The battery self-discharges even when it not being used, and it 
goes into overdischarge state if it is left for a long period of time. 
The backup time may become shorter or the battery may become 
unusable.

We recommend keeping the temperature 25

°C

 or less when 

storing the unit for long periods of time.

Turn OFF the unit’s power when storing it.

Do not install or store the unit in a place exposed to direct sunlight.

The rise of temperature may cause the battery unit to deteriorate 
rapidly and become unusable.

Correct Installation Method

For installation, to improve the long time reliability of the UPS, pay 
much attention to heat dissipation. Ensure convection of air around 
the UPS main body, and use the UPS in an operating condition 
below the derating curve.

During machining work for mounting, make sure that no metal 
scrap goes into the product.

The heat dissipation of the UPS may become worse depending on 
how the UPS is mounted; in rare cases, internal components may 
deteriorate and get damaged. Use the UPS in an operating 
condition based on the derating curve for each mounting direction.

Standard mounting

Note: 1.

This UPS can be mounted with the sides in close contact.
Up to 3 units can be mounted in close contact.
Follow the derating curve during mounting with the sides in 
close contact.

2.

When you install devices other than the UPS on the left or 
the right of the UPS, leave a space of at least 15 mm.

Face-up mounting

Precautions for Safe Use

 

 

Leave 50 mm of space between the upper and lower.

Leave 50 mm of space between the upper and lower.

Summary of Contents for S8BA LF Series

Page 1: ...Model Number Legend Use the following format to place an order Ordering Information Main body Uninterruptible Power Supply UPS 16 7 A 400 W for use as a UL compliant device Communication cable Replac...

Page 2: ...play cancellation at a load equal to or below the rated capacity normal operation backup operation Battery Type Lithium ion battery Rated voltage 14 4 VDC Rated capacity 1600 mAh 1 parallel 1600 mAh 2...

Page 3: ...ad lines V V 3 DC input terminal block Connect to input lines V V 4 GR terminal Ground this terminal to less than 100 to improve noise resistance and prevent electrical shock 5 USB port Connect to a U...

Page 4: ...0 W S8BA 24D24D240LF 240 W S8BA 24D24D360LF 360 W S8BA 24D24D480LF 480 W No Name Function 11 DIN rail mounting hook Hook the UPS on the DIN rail 12 DIN rail mounting groove Groove for positioning the...

Page 5: ...wire Twisted pair 0 5 mm2 AWG AWG20 10 A Solid wire Twisted pair 0 75 mm2 AWG AWG16 15 A Solid wire Twisted pair 1 25 mm2 AWG AWG14 20 A Solid wire Twisted pair 2 0 mm2 AWG AWG12 Temperature rating f...

Page 6: ...the UPS is stopped after the time period specified in advance has elapsed Remote ON OFF signal Remote ON OFF signals can be used to start and stop the UPS by using either an externally connected cont...

Page 7: ...e with no problems even if the rated capacity of the UPS is larger than the rated capacity of the switching power supply Switch mode power supply capacity UPS internal power consumption Internal power...

Page 8: ...the total capacity of the connected devices 3 Calculate the initial value of the backup time for the total capacity of the connected devices from the graph below Graph of backup time graph of initial...

Page 9: ...20 0 Ambient temperature C Load rate A For standard mounting B For face up mounting stationary mounting A C B 0 10 20 30 40 50 60 120 100 80 60 40 20 0 Ambient temperature C Load rate A For standard m...

Page 10: ...s During power failure Power switch Battery level UPS output Indication in the status display Beeper UPS operating mode BU signal OUT BL signal OUT BS signal IN Normal operation Backup operation ON ON...

Page 11: ...2 In normal operation the output stops when the input protection fuse blows out Dimensions Unit mm Main body 0 20 40 60 80 100 0 20 40 60 80 100 120 In backup operation Output current Output voltage 1...

Page 12: ...er 2012 R2 2012 Windows Storage Server 2008 R2 2008 RS232C USB Simple Shutdown Software You can execute computer shutdown and UPS auto stop when an input power problem occurs power failure etc You can...

Page 13: ...imary power supply before connecting the unit to the input power supply terminal When connecting a cable to the terminal block use a cable that complies with the input current specification of the UPS...

Page 14: ...ct with water If you drop the unit stop using it Doing so may cause an electric shock or a fire Doing so may cause an abnormal heating smoke rupture or fire on the battery If the unit becomes wet or i...

Page 15: ...nside the battery may melt the gas exhaust valve or protection mechanism may be damaged or the electrolyte may catch fire and it may result eventually in abnormal heating smoke rupture or fire Do not...

Page 16: ...main body and use the UPS in an operating condition below the derating curve During machining work for mounting make sure that no metal scrap goes into the product The heat dissipation of the UPS may...

Page 17: ...ll machine conform to EMC standards Applicable EMC Electromagnetic Compatibility standards are as follows EMS Electromagnetic Susceptibility EN 61000 6 2 EMI Electromagnetic Interference EN 61000 6 4...

Page 18: ...xpressly approved by the party responsible for compliance could void the user s authority to operate the equipment This equipment has been tested and found to comply with the limits for a Class A digi...

Page 19: ...he USB RS 232C I O port installed in the UPS Two types of batteries are selectable for the 480W allowing the ideal backup time to be realized A wide lineup culminating in the 960W makes it possible to...

Page 20: ...Communication cable Input voltage Output voltage Output current capacity Model number 24 VDC 24 VDC 20 A 480 W S8BA 24D24D480SBF 40 A 960 W S8BA 24D24D960SBF Rated voltage Rated capacity Weight Model...

Page 21: ...cteristics 6 min constant power rated load The backup time can be set from the mode selection backup operation time selection switch or the shutdown software Environme nt Operating environment tempera...

Page 22: ...han specified time 4 Conditions With rated loads connected at a rated input voltage and at a full battery charge 5 Conditions With rated loads connected at a rated input voltage and at maximum battery...

Page 23: ...ck 6 Battery communication port 3 Battery connection terminal block 7 Mode selection Backup time setting switch 4 LED indicators 8 RS232C USB port DC ON LED BATT LED ALERT LED Positive terminal Negati...

Page 24: ...S8BA SBF 24 Rear view S8BA 24D24D480SBF S8BA S480L S8BA 24D24D960SBF S8BA S960L 9 9 No Name 9 DIN rail hook 9 9 No Name 9 DIN rail hook...

Page 25: ...and recommended cable sizes see the following table 20 A 40 A Connectable sizes Cable Solid wire 0 2 to 10 mm2 0 75 to 16 0 mm2 Stranded wire 0 2 to 6 mm2 AWG AWG 8 to 24 AWG 6 to 18 Stripped cable le...

Page 26: ...ied in advance has elapsed Remote ON OFF signal Remote ON OFF signals can be used to start and stop the UPS by using either an externally connected contact or the ON OFF status of the open collector c...

Page 27: ...e with no problems even if the rated capacity of the UPS is larger than the rated capacity of the switching power supply Switch mode power supply capacity UPS internal power consumption Internal power...

Page 28: ...e backup time for the total capacity of the connected devices from the graph below Graph of backup time graph of initial values for products that have not been used at 25 C The backup time becomes sho...

Page 29: ...Contact mounting Less than 15 mm space between the left and right 0 10 20 30 40 50 60 100 80 60 40 20 0 Ambient temperature C Load rate 0 10 20 30 40 50 60 100 80 60 40 20 0 Ambient temperature C Load...

Page 30: ...ge 26 Overcurrent protection curve 480 W 960 W Durling power failure Input power supply Output from UPS UPS operating mode Normal operation Backup operation BU signal OUT BL signal OUT BS signal IN Ba...

Page 31: ...1 Dimensions Unit mm Control unit Battery unit S8BA 24D24D480SBF 124 9 5 31 99 4 44 111 4 S8BA 24D24D960SBF 9 5 52 124 111 4 31 99 4 111 4 9 5 30 7 80 124 99 4 S8BA S480L 111 4 9 5 150 124 30 7 99 4 S...

Page 32: ...er 2012 R2 2012 Windows Storage Server 2008 R2 2008 RS232C USB Simple Shutdown Software You can execute computer shutdown and UPS auto stop when an input power problem occurs power failure etc You can...

Page 33: ...ch to BATT REP and when the LED changes from a fast blink to a slow blink shut off the input power When performing maintenance on the connected devices follow the above instructions to ensure safety W...

Page 34: ...or more above the top and below the bottom Do not connect the RS232C USB port or the CONTACT port to a LAN device using a LAN cable Connection to a LAN device may result in malfunction in or damage t...

Page 35: ...he input terminal block and the output terminal block of the UPS Doing so may result in electric shock Do not insert metal objects into the battery connectors Do not short between the connector termin...

Page 36: ...is left unused in the above state for 3 months or longer the battery goes into overdischarge state and the backup time may become shorter or the battery may become unusable Storing Storing the battery...

Page 37: ...schedule and frequency Applicable directives EMC Directives Low Voltage Directives Principles regarding conformance OMRON electronic devices that comply with EC Directives also conform to the related...

Page 38: ...f radio interference occurs the user may be required to take appropriate measures Conformance to UL This product must be installed within a control panel with an internal heater or other unit to prote...

Page 39: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 40: ...2356 81 388 Contact www ia omron com Kyoto JAPAN OMRON ASIA PACIFIC PTE LTD No 438A Alexandra Road 05 05 08 Lobby 2 Alexandra Technopark Singapore 119967 Tel 65 6835 3011 Fax 65 6835 2711 OMRON CHINA...

Reviews: