S8VM
8
Construction and Nomenclature
(15-W, 30-W, 50-W, 100-W, 150-W Models)
■
Nomenclature
Note: 1.
The fuse is located on the (L) side. It is NOT user-replace-
able.
2.
If mounting is performed using a DIN Rail, the protective
earthing connection is the panel mounting hole shown in the
figure below.
(A protective earthing connection stipulated in safety stan-
dards is used. Connect the ground completely (S8VM-
@@@@@
D only)).
Ground terminal: M3 (Depth: 8 mm max.)/Ground wire:
AWG 18
3.
S8VM-
@@@
24A
@
/P
@
only
4.
S8VM-05024A
@
/P
@
, S8VM-10024A
@
/P
@
, S8VM-
15024A
@
/P
@
only. Housing and terminals of the connector
for undervoltage detection output are also provided. For de-
tails, refer to
Undervoltage Alarm Output Connector Har-
5.
When not using the remote sensing function, leave the short
bar in the same state as when shipped.
6.
A
@
models: Common terminal (emitter)
P
@
models: Common terminal (collector)
■
Output Color Label
5
4
3
2
1
6
7
8 9 10
12
12
1
2
11
8
9
10
3
11
4
5
6 7
12
12
1
2
11
3
11
4
5
12
12
6
7
8 9 10
12
12
15-W, 30-W, 50-W Models
Open-frame Models
Covered Models
S8VM-015
@@
/S8VM-015
@@
D
S8VM-030
@@
/S8VM-030
@@
D
S8VM-050
@@
/S8VM-050
@@
D
100-W Models
Open-frame Models
Covered Models
S8VM-100
@@
/S8VM-100
@@
D
S8VM-100
@@
C
@
/S8VM-10024A
@
/P
@
150-W Models
Open-frame Models
Covered Models
S8VM-150
@@
/S8VM-150
@@
D
S8VM-150
@@
C
@
/S8VM-15024A
@
/P
@
S8VM-015
@@
C
@
/S8VM-01524A
@
S8VM-030
@@
C
@
/S8VM-03024A
@
S8VM-050
@@
C
@
/S8VM-05024A
@
/P
@
300-W, 600-W, 1,500-W Models
Note:
Refer to page 14.
No.
Name
Function
1
AC input terminals (L), (N)
Connect the input lines to
these terminals. (See note 1.)
2
PE terminal: Protective earthing terminal
(S8VM-
@@@@@
C
@
/S8VM-
@@@@@
A
@
/
S8VM-
@@@@@
P
@
)
FG terminal: Frame ground terminal
(S8VM-
@@@@@
/S8VM-
@@@@@
D)
Connect the ground line to this
terminal. (See note 2.)
3
DC output terminals (-V), (+V)
Connect the load lines to these
terminals.
4
Output indicator (DC ON: Green)
Lights (green) while a direct
current (DC) output is ON.
5
Output voltage adjuster (V. ADJ)
Use to adjust the voltage.
6
Undervoltage alarm indicator 1
(DC LOW1: Yellow) (See note 3.)
Lights only when a momentary
drop in output voltage is de-
tected. This status is main-
tained.
7
Undervoltage alarm indicator 2
(DC LOW2: Red) (See note 3.)
Lights only when the output
voltage drops to approximately
20 V or lower.
8
Undervoltage alarm output terminal 1:
(DC LOW1) (See note 4.)
Outputs only when a momen-
tary drop in output voltage is
detected. This status is main-
tained.
(The transistor turns OFF
when a voltage drop occurs.)
9
Undervoltage alarm output terminal 2:
(DC LOW2) (See note 4.)
Outputs only when the output
voltage drops to approximately
20 V or lower.
(The transistor turns OFF
when a voltage drop occurs.)
10
Common terminal for undervoltage alarm
output (See note 4.)
Common terminal (See note
6.) for terminals 8 and 9
11
Remote sensing terminals (See note 5.)
Correct the voltage drop in the
load lines.
12
Short bars (See note 5.)
---
Protective earthing
connection
Ground
Color label identifying output voltage
Green: 5 V
Blue:
12 V
Yellow: 15 V
White: 24 V
This color label identifies the output voltage by color.