5-3 Preparing for Operation
5-3-1
Turning ON the Power and Checking Indicators
5-5
5-3
Preparing for Operation
This section explains the procedure following installation, wiring, and switch setting of the Servomotor
and Servo Driver, to prepare the mechanical system for trial operation.
It explains what you need to check both before and after turning ON the power.
5-3-1
Turning ON the Power and Checking Indicators
Items to Check Before Turning ON the Power
Checking Power Supply Voltage
•
Check to be sure that the power supply voltage is within the ranges shown below.
R7D-ZP
@@
H (Single-phase 200-V AC input)
Main-circuit power supply: Single-phase 200/230 V AC (170 to 253 V) 50/60 Hz
Checking Terminal Block Wiring
•
The main-circuit power supply inputs (L1/L2) must be properly connected to the
terminal block.
•
The Servomotor’s red (U), white (V), and blue (W) power lines and the yellow/green
ground wire (
) must be properly connected to the terminal block.
Checking the Servomotor
•
There should be no load on the Servomotor. (Do not connect to the mechanical
system.)
•
The Servomotor’s power lines and Servomotor Power Cable must be connected
securely.
•
The Encoder Cable must be securely connected to the Encoder Connector (CN2) at
the Servo Driver.
•
The Encoder Cable must be securely connected to the Encoder Connector at the
Servomotor.
Checking the Control Connectors
•
The Control Cable must be securely connected to the I/O Control Connector (CN1).
•
The RUN command (RUN) must be OFF.
Turning ON Power
•
First carry out the preliminary checks, and then turn ON the main circuit power
supply.
•
The ALM output will take approximately 2 seconds to turn ON after the power has
been turned ON. Do not attempt to detect an alarm using the Host Controller during
this time (when power is being supplied with the Host Controller connected).
Checking Displays
•
Once the power has been turned ON, check that the command indicator (REF) is lit
orange or green.
•
If the command indicator is orange, turn ON the RUN command input (RUN) and
check that the indicator changes from orange to green.
•
If the indicator does not change to green or one of the alarm indicators is lit (AL1 to
AL3), refer to
Section 6 Troubleshooting
and correct the error.
Summary of Contents for SMARTSTEP Junior R7D-ZP
Page 3: ...2 ...
Page 18: ...Section 1 Configuration Features and System ...
Page 25: ...1 5 Applicable Standards 1 5 2 UL and cUL Standards 1 8 ...
Page 26: ...Section 2 Dimensions Standard Models and ...
Page 36: ...Section 3 Specifications ...
Page 62: ...Section 4 System Design ...
Page 86: ...Section 5 Operation ...
Page 96: ...Section 6 Troubleshooting ...
Page 109: ...6 5 Periodic Maintenance 6 5 3 Replacing the Cooling Fan 6 14 ...
Page 110: ...Appendix ...