MULTI-BEAM SAFETY SENSOR

(Version 2)

Model

 

F3SJ-AM

P

□□□

1. Application of a F3SJ sensor alone cannot receive type approval 

provided by Article 44-2 of the Labour Safety and Health Law of Japan. 
It is necessary to apply it in a system. Therefore, when using the F3SJ in 
Japan as a "safety system for pressing or shearing machines" prescribed 
in Article 42 of that law, the system must receive type approval.

2. The F3SJ is electro-sensitive protective equipment (ESPE) in accordance 

with European Union (EU) Machinery Directive Index Annex V,  Item 2.

3. EC Declaration of Conformity

  OMRON declares that F3SJ is in conformity with the requirements of the
  following EC Directives:

  Machinery Directive 2006/42/EC

  EMC Directive 2014/30/EU

4. F3SJ is in conformity with the following standards:

(1) European standards

EN61496-1 (Type 4 ESPE), EN 61496-2 (Type 4 AOPD), EN61508-1 
through -3 (SIL3), EN ISO 13849-1:2015 (Category 4, PL e)

(2) International standards

IEC61496-1 (Type 4 ESPE), IEC61496-2 (Type 4 AOPD), IEC61508-1 
through -3 (SIL3), ISO 13849-1:2015 (Category 4, PL e)

(3) JIS standards

JIS B 9704-1 (Type 4 ESPE), JIS B 9704-2 (Type 4 AOPD)

(4) North American Standards:

UL61496-1(Type 4ESPE), UL61496-2(Type 4AOPD), UL508, UL1998, 
CAN/CSA C22.2 No.14, CAN/CSA C22.2 No.0.8

5. The F3SJ received the following approvals from the EU accredited body, 

TÜV SÜD Product Service GmbH:
•EC Type-Examination in accordance with the EU Machinery Directive, 
Type 4 ESPE (EN61496-1), Type 4 AOPD (EN 61496-2)
•TÜV SÜD Product Service Type Approval, Type 4 ESPE (EN61496-1), Type 
4 AOPD (EN 61496-2), SIL1, 2, 3 (EN61508-1 through -3), EN ISO 
13849-1:2015 (Category 4, PL e)

6. The F3SJ received the certificates of UL listing for US and Canadian safety 

standards from the Third Party Assessment Body UL.
•Both are: Type 4 ESPE (UL61496-1), Type 4 AOPD (UL61496-2)

7. The F3SJ is designed according to the standards listed below. To make 

sure that the final system complies with the following standards and 
regulations, you are asked to design and use it in accordance with all 
other related standards, laws, and regulations. If you have any 
questions, consult with specialized organizations such as the body 
responsible for prescribing and/or enforcing machinery safety 
regulations in the location where the equipment is to be used.
•European Standards: EN415-4, EN692, EN693
•U.S. Occupational Safety and Health Standards: OSHA 29 CFR 1910.212
•U.S. Occupational Safety and Health Standards: OSHA 29 CFR 1910.217
•American National Standards: ANSI B11.1 to B11.19
•American National Standards: ANSI/RIA 15.06
•Canadian Standards Association CSA Z142, Z432, Z434
•SEMI Standards SEMI S2
•Ministry of Health, Labour and Welfare "Guidelines for Comprehensive 
Safety Standards of Machinery", Standard Bureau's Notification No. 501 
dated June 1, 2001.

© OMRON Corporation  

2006-2020

  All Rights Reserved.

LEGISLATION AND STANDARDS

Alert Statements in this Manual

INSTRUCTION SHEET

Regarding the alert symbols and meanings used for the safe uses

In order for our customers to use the F3SJ in safety, precautions are 
indicated in this manual with the alert symbols and statements such as the 
followings. Those safety precautions relate to the important descriptions 
that must be obeyed for the safe uses and operations. Be sure to obey the 
precautions. The following indictions and symbols are used for the 

When changes are made to each function using the setting tool 
(F39-GWUM or F39-MC21), the administrator must manage the details of 
the changes and perform the changes. Accidental functional setting 
change may cause failure of human body detection, resulting in a serious 
injury.

The F3SJ must be installed, configured, and incorporated into a machine 
control system by a sufficiently trained and qualified person. An 
unqualified person may not be able to perform these operations 
properly, which may cause a person to go undetected, resulting in 

Do not use this sensor for machines that cannot be stopped by 
electrical control. For example, do not use it for a pressing machine 
that uses full-rotation clutch. Otherwise, the machine may not stop 
before a person reaches the hazardous part, resulting in serious injury.

Make sure to test the operation of the F3SJ after installation to verify 
that the F3SJ operates as intended. Make sure to stop the machine 
until the test is complete. Unintended function settings may cause a 
person to go undetected, resulting in serious injury.

Install a protective structure so that the hazardous part of a machine can 
only be reached by passing through the sensor's detection zone. Install 
the sensors so that part of the person is always present in the detection 
zone when working in a machine's hazardous areas. If a person is able 
step into the hazardous area of a machine and remain behind the F3SJ's 
detection zone, configure the system with an interlock function that 
prevents the machine from being restarted. Failure to do so may result in 
serious injury.

Do not use the auxiliary output or external indicator output for safety 
applications. Human body may not be detected when F3SJ fails, 
resulting in serious injury.

Make sure to install the F3SJ at the safe distance from the hazardous 
part of the equipment. Otherwise, the machine may not stop before a 
person reaches the hazardous part, resulting in serious injury.

Install the interlock reset switch in a location that provides a clear view 
of the entire hazardous area and where it cannot be activated from 
within the hazardous area.

The F3SJ cannot protect a person from an object flying from a 
hazardous area. Install protective cover(s) or fence(s).

The muting and override functions disable the safety functions of the device. 
You must ensure safety using other method when these functions are 

Install muting sensors so that they can distinguish between the object that is 
being allowed to pass through the detection zone and a person. If the muting 
function is activated by the detection of a person, it may result in serious injury.

Muting lamps (external indicators) that indicate the state of the muting 
and override functions must be installed where they are clearly visible 
to workers from all the operating positions.

Use independent 2 input devices for muting inputs.

Muting related time must be properly configured for its application by a 
sufficiently trained and qualified person, and the person must have 
responsibility for settings, especially when setting the muting time limit to 
infinite.

You must install F3SJ, muting sensor, and physical barrier, and configure
time settings for muting so that an operator should not enter hazardous zone.

Install the sensor system so that it is not affected by the reflective 
surface of the F3SJ.

Make sure that the F3SJ is securely mounted and its cables and 
connectors are properly connected.

Make sure that foreign material such as water, oil, or dust does not 
enter the F3SJ or the connector while the cap is removed.

When using more than 1 set of F3SJ, install them so that mutual 
interference does not occur, such as by configuring series connections 
or using physical barriers between adjacent sets.

Do not use the sensor system with mirrors in a retro-reflective 
configuration. Doing so may hinder detection. It is possible to use 
mirrors to "bend" the detection zone to a 90-degree angle.

Perform an inspection for all F3SJ as described in "Chapter 6 
Checklists" of User’s manual. When using series connections,perform 
inspections 

Connect the load between the output and 0V line (PNP output). 
Connecting the load between the output and +24V line will result in a 
dangerous condition because operation is reversed to ON when 

Do not short-circuit the output line to the +24V line. Otherwise, the 
output is always ON. Also, the 0V of the power supply must be grounded 
so that output does not turn ON due to grounding of the output line.

Configure the system by using the optimal number of safety outputs 
that satisfy the requirements of the necessary safety category.

Do not connect each line of F3SJ to a DC power supply of more than 
24VDC+20%. Also, do not connect to an AC power supply. Failure to 
do so may result in electric shock.

Double or reinforced insulation from hazardous voltage must be applied 
to all input and output lines. Failure to do so may result in electric shock.

Do not try to disassemble, repair, or modify this product. Doing so 
may cause the safety functions to stop working properly.

Do not use the F3SJ in environments where flammable or explosive 
gases are present. Doing so may result in explosion.

Perform daily and 6-month inspections for the F3SJ. Otherwise, the 
system may fail to work properly, resulting in serious injury.

Extension of the cable must be within a specified length. If it isn't, 
safety function may not work properly, resulting in danger.

To use the F3SJ in PSDI mode (Reinitiation of cyclic operation by the 
protective equipment), you must configure an appropriate circuit between 
the F3SJ and the machine. For details about PSDI, refer to OSHA1910.217, 
IEC61496-1, and other relevant standards and regulations.

For the F3SJ to comply with IEC 61496-1 and UL 508, the DC power 
supply unit must satisfy all of the following conditions:
• Must be within the rated power voltage (24V DC ± 20%)
• Must have tolerance against the total rated current of devices if it is 
connected to multiple devices
• Must comply with EMC directives (industrial environment)
• Double or reinforced insulation must be applied between the primary 
and secondary circuits
• Automatic recovery of overcurrent protection characteristics 
(reversed L sagging)
• Output holding time must be 20ms or longer
• Must satisfy output characteristic requirements for class 2 circuit or 
limited voltage current circuit defined by UL508
• Must comply with laws and regulations, regarding EMC and electrical 
equipment safety, of the country or region where the F3SJ is used (Ex: 
In EU, the power supply must comply with the EMC Directive and the 
Low Voltage Directive.)

PRECAUTIONS ON SAFETY

Make sure to observe the following precautions that are necessary for ensuring 
safe use of the product.
• Thoroughly read this manual and understand the installation procedures, 
operation check procedures, and maintenance procedures before using the 
product.
• Loads must satisfy both of the following conditions:

-Not short-circuited
-Not used with a current that is higher than the rating

• Do not drop the product.
• Dispose of the product in accordance with the relevant rules and regulations of 
the country or area where the product is used.

PRECAUTIONS FOR SAFE USE

Observe the precautions described below to prevent operation failure, 
malfunctions, or undesirable effects on product performance.

Installation environment

Do not install the F3SJ in the following types of environments:
•Areas exposed to intense interference light, such as direct sunlight
•Areas with high humidity where condensation is likely to occur
•Areas where corrosive gases are present
•Areas exposed to vibration or shock levels higher than in the specification 
provisions
•Areas where the product may come into contact with water
•Areas where the product may get wet with oil that can solve adhesive
Do not use radio equipment such as cellular phones, walkie-talkies, or 
transceivers near the F3SJ.
This is a class A product. In residential areas it may cause radio interference. 
in which case the Responsible Person may be required to take adequate 
measures to reduce interference

Wiring and installation

•Make sure to perform wiring while the power supply is OFF. Otherwise, the 
F3SJ may fail to operate due to the diagnosis function.
•Do not short-circuit output lines to +24V line. Otherwise a fault of F3SJ 
may occur.

•When extending the communication line with a cable  (twisted-pair wire) 
other than the dedicated cable (F39-JD**), use a cable with the same or 
superior specification. Connect the shield to the 0V line.
•When replacing the cable connectors with other types of connectors, use 
connectors that provide a protection grade of IP54 or higher.
•Properly perform the wiring after confirming the signal names of all the 
terminals.
•Do not operate the control system until 2 seconds or more (2.2 seconds or 
more in case of series connection)  after turning ON the power of the F3SJ.
•Be sure to route the F3SJ cable separate from high-potential power lines or 
through an exclusive conduit.
•When using a commercially available switching regulator power supply, 
make sure to ground the FG terminal (frame ground terminal).
•Install the emitter and receiver so that their vertical direction should 
match.
•If the protective height is 600 mm or more, use intermediate mounting 
brackets of specified quantities and locations according to the dimensions.
If the brackets described above are not used, ratings and performance 
cannot be not met.
•Sharing the power supply with other devices may cause the F3SJ to be 
affected by noise or voltage drop. It is recommended that the F3SJ use a 
dedicated power supply but do not share with other devices.

Cleaning

Do not use thinner, benzene, or acetone for cleaning, because they affect 
the product's resin parts and paint on the case.

Object detection

The F3SJ cannot detect transparent and/or translucent objects.

PRECAUTIONS FOR CORRECT USE

RATINGS

Indicates a potentially hazardous situation 
which, if not avoided, will result in minor or 
moderate injury, or may result in serious 
injury or death. Additionally there may be 
significant property damage.

WARNING

WARNING

WARNING

WARNING

WARNING

WARNING

For Users

Ratings/Specifications

In the type names in this table, the * contain the number of beams.

For Machines

For Installation

For Wiring

Other

F3SJ-AM*P300

Beam gap

300

Number of beams

F3SJ-AM2P300 : 2 beams
F3SJ-AM3P300 : 3 beams
F3SJ-AM4P300 : 4 beams

Protective height

Lens diameter

Diameter 5mm

Operating range

0.2 to 9m(Operating range can be reduced to 0.5m through the setting tool) 

Response time

ON to OFF: 10ms to 11ms max., OFF to ON: 40ms to 44ms max. (when incidence is stable).
Refer to the reverse side for details.

Startup waiting time

2s max. (2.2s max in case of series connection)
24VDC ± 20% (ripple p-p10% max.)

Power supply  voltage(Vs)
Current 
consumption (no load)

Emitter

76 mA max.

Receiver

68 mA max.

Light source

Infrared LED (870nm wavelength)
Within ±2.5 ° for the emitter and receiver at a detection distance of at least 3 m according to IEC61496-2

Effective aperture angle (EAA)

Safety outputs(OSSD)

PNP transistor outputs x 2, Load current 300mA max, Residual voltage 2V max. (except for voltage drop due 
to cable extension)(including inductance load), Maximum capacity load 2.2 

μ

F, Leakage current 1mA max.

 (This may be different from previously used logic (ON/OFF) because safety circuit is used.)

output)

Auxiliary output 1 (Non-safety 

Auxiliary output 2 (non-safety 
output, a function for a basic 

PNP transistor output x 1, Load current 300mA max., Residual voltage 2V max. (except for voltage drop due 

system)

PNP transistor output x 1, Load current 50mA or less, Residual voltage 2V or less (excluding influence by 
cable extension), Leakage current 1mA or less

to cable extension), Leakage current 1mA max.

External indicator output 
(Non-safety output)

Connectable external indicator
- Incandescent lamp : 24VDC, 3 to 7W
- LED lamp : Load current 10 to 300mA max.

external indicator.)

Leakage current 1mA max.(An indicator cable F39-JJ3N or F39-A01P*PAC is required when using an 

Output operation mode

Safety outputs : ON when receiving light
Auxiliary output 1 : Reverse output of safety output (operation mode can be changed by the setting tool)
Auxiliary output 2: Turns ON when 30,000 hours of power-on time passes (operation mode can be changed 

muting system)

by the setting tool)
External indicator output 1: Reverse output of safety output (for basic system), ON during muting/override (for 

(Operation mode can be changed by the setting tool)
External indicator output 2: ON in lockout (for basic system), ON during muting/override (for muting system) 
(operation mode can be changed by the setting tool)

Input voltage

Indicators

Test input, Interlock select input, Reset input, Muting input:
ON voltage: 9V to Vs* (short-circuit current: approx. 2.0mA)
OFF voltage: 0 to 1.5V, or open
External device monitoring input is:

OFF voltage: open
*The Vs indicates a voltage value in your environment.

ON voltage: 9V to Vs* (short-circuit current: approx. 3.5mA)

Emitter

Error mode indicators (red LED x 3): Blink to indicate error details

Incident light level indicators (green LED x 2, orange LED x 3): ON based on the amount of incident light

Power indicator (green LED x 1): ON while power is ON
Interlock indicator (yellow LED x 1): ON when in interlock/Blinks when in lockout
External device monitoring indicator [muting input 1 indicator],  Test indicator [muting input 2 
indicator] (green LED x2): ON/Blink according to function

Receiver

Error mode indicators (red LED x 3): Blink to indicate error details

Incident light level indicators (green LED x 2, orange LED x 3): ON based on the amount of incident light

OFF-state indicator (red LED x 1): ON when safety outputs are OFF/ Blinks when in lockout

Muting error indicator, Test indicator (green LED x 2): ON/Blink according to function

ON-state indicator (green LED x 1): ON when safety outputs are ON

Mutual interference prevention
function
Series connection

Time division emission by series connection

- Number of connections: Up to 4 sets
- Total number of beams: Up to 400

- Cable length between sensors: 15 m max. (not including series connection cable (F39-JJR*L or F39-JJR3W) and power cable)

- Self-test (After power ON, and during operation)
- External test (light emission stop function by test input)

- External device monitoring
- Muting (Includes lamp breakage detection and override functions. F39-CN6 key cap for muting is required)

- Start interlock, restart interlock (The setting tool is required when muting function is used)

Interference light avoidance algorithm, Operating range change function

Test function

Safety-related functions

Connection method
Protection circuit

Connector method (M12, 8-pin)

During operation: 35 to 85%RH (no condensation), During storage: 35 to 95%RH

During operation: -10 to 55°C (without freezing), During storage: -30 to 70°C

Ambient temperature

Output short-circuit protection, and power supply reverse polarity protection

Ambient humidity
Ambient light intensity

of 10,000 Ix max.

Incandescent lamp: receiving-surface light intensity of 3,000 Ix max., Sunlight: receiving-surface light intensity 

Insulation resistance

20M

 or higher (500VDC)

Dielectric strength voltage

1, 000VAC, 50/60Hz, 1min

Degree of protection

IP65 (IEC60529)

Dia. 6 mm, 8-wire (0.15mm2 x 8) with braided shield, Allowable bending radius R5mm

Malfunction: 100m/s2, 1,000 times each in X, Y, and Z directions

Vibration resistance

Malfunction: 10 to 55Hz, Multiple amplitude of 0.7mm, 20 sweeps each in X, Y, and Z directions

Shock resistance
Connection cable, Series 
connection cable (F39-JJR*L, 
JJR3W)

Extension cable 
(F39-JD*A, JD*B,JC*C) 

bending radius of R36mm.
(To extend a cable, use an equivalent or higher-performance cable (twisted-pair wire) , and do not use the 

Dia. 6.6 mm, 8-wire (0.3mm2 x 4P, conductor resistance 0.058 ohm/m), with braided shield,Allowable 

cable in the same duct as that for high-voltage cables or power cables)
For details about extension lengths ( Power Cable Length), refer to next page

Material

Cap: ABS resin

Cable: Oil resistant PVC

Weight (g) values can be:

Casing (including metal parts on both ends): Aluminum, zinc die-cast

Optical cover: PMMA resin (acrylic)

Weight (packaged)

-F3SJ-AM2P300 :1550(g)
-F3SJ-AM3P300 :2370(g)
-F3SJ-AM4P300 :2790(g)
-F3SJ-AM2P400 :1690(g)
-F3SJ-AM3P400 :2650(g)
-F3SJ-AM4P400 :3710(g)
-F3SJ-AM2P500 :1830(g)

Accessories

Instruction sheet, top and bottom mouting brackets,intermediate mounting brackets(*), error mode label, 
Quick Installation Manual(QIM)
* The number of intermediate mounting brackets are as follows:

Applicable standards

IEC61496-1, EN61496-1, UL61496-1 Type 4ESPE (Electro-Sensitive Protective Equipment)
IEC61496-2, EN 61496-2, UL61496-2 Type 4AOPD (Active Opto-electronic Protective Devices) IEC61508, 
EN61508 SIL3, EN ISO 13849-1:2015 (Category 4, PL e), ISO 13849-1:2015 (Category 4, PL e)

F3SJ-AM2P300 : 300mm
F3SJ-AM3P300 : 600mm
F3SJ-AM4P300 : 900mm

F3SJ-AM*P400
400

F3SJ-AM2P400 : 2 beams
F3SJ-AM3P400 : 3 beams
F3SJ-AM4P400 : 4 beams
F3SJ-AM2P400 : 400mm
F3SJ-AM3P400 : 800mm
F3SJ-AM4P400 : 1200mm

F3SJ-AM*P500
500

F3SJ-AM2P500 : 2 beams

F3SJ-AM2P500 : 500mm

-F3SJ-AM2P300 : Not included
-F3SJ-AM3P300 : 1 set for each the emitter and receiver is included
-F3SJ-AM4P300 : 1 set for each the emitter and receiver is included
-F3SJ-AM2P400 : Not included
-F3SJ-AM3P400 : 1 set for each the emitter and receiver is included
-F3SJ-AM4P400 : 2 set for each the emitter and receiver is included
-F3SJ-AM2P500 : Not included

 *Connection is not available with other models than F3SJ-AM

P

□□□

.

Original instructions

Indicates prohibited actions.

Indicates mandatory actions.

Indicates the risk of electric shock.

You must ensure that the system works as you intended after 
configuring floating blanking.Failure to do so may result in serious injury.

Warning zone output is non-safety output. You must not include it to 
calculation of safety distance. Otherwise safety distance may be reduced, 
resulting in serious injury.

A switch to activate the override function must be a hold-to-run device 
such as a spring return key switch and must be installed in a location that 
provides a clear view of the entire hazardous zone and where it cannot 
be activated from within the hazardous zone.Make sure that nobody is in 
the hazardous area before activating the override function.

Omron Companies shall not be responsible for conformity with any standards, 
codes or regulationswhich apply to the combination of the Product in the 
Buyer’ s application or use of the Product. At Buyer’ s request, Omron will 
provide applicable third party certification documents identifying ratings and 
limitations of use which apply to the Product. This information by itself is not 
sufficient for a complete determination of the suitability of the Product in 
combination with the end product, machine, system, or other application or 
use. Buyer shall be solely responsible for determining appropriateness of the 
particular Product with respect to Buyer’ s application, product or system. 
Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO 
LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE 
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT 
THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE 
INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

Suitability for Use

Please read and understand this instruction sheet before 
storing, installing, programming, operating, maintaining, or 
disposing of the products. Please consult your OMRON 
representative if you have any questions or comments.

Please refer to the User's Manual and the Quick Installation 
Manual for detailed instructions on usage.

OMRON Corporation 

 (Manufacturer)

 Contact:  www.ia.omron.com

Regional Headquarters

Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 JAPAN

OMRON EUROPE B.V. (Importer in EU)
Wegalaan 67-69, 2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388

OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200 
Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787

OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2), 
Alexandra Technopark, 
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711

OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower, 
200 Yin Cheng Zhong Road, 
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200

t

F e b ,   2 0 2 0

F  

*

9

4

0

4

0

8

6

-

2

H

*

Reviews: