Main Setup [200]
Section 11-2
During the Extended ID run the motor is powered on and rotates. The VSD
measures the rotor and stator resistance as well as the induction and the iner-
tia for the motor.
Communication information
!Warning
During the extended ID RUN, the motor will rotate. Take safety measures to
avoid unforeseen dangerous situations.
Note
To run the VSD it is not mandatory for the ID RUN to be executed, but without
it the performance will not be optimal.
Note
If the ID Run is aborted or not completed the message “Interrupted!” will be
displayed. The previous data do not need to be changed in this case. Check
that the motor data are correct.
Encoder Feedback [22B]
Only visible if the Encoder option board is installed. This parameter enables or
disables the encoder feedback from the motor to the VSD.
Communication information
Default:
Off, see Note
Off
0
Not active
Short
1
Parameters are measured with injected DC current. No
rotation of the shaft will occur.
Extended
2
Additional measurements, not possible to perform with DC
current, are done directly after a short ID run. The shaft will
rotate and must be disconnected from the load.
Modbus Instance no/
DeviceNet no:
43049
Profibus slot/index
168/208
EtherCAT index (hex)
4be9
Fieldbus format
UInt
Modbus format
UInt
229 Motor ID-Run
Stp M1: Off
A
Default:
Off
On
0
Encoder feedback enabled
Off
1
Encoder feedback disabled
Modbus Instance no/
DeviceNet no:
43051
Profibus slot/index
168/210
EtherCAT index (hex)
4beb
Fieldbus format
UInt
Modbus format
UInt
22B Encoder
Stp M1:
Off
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...