100
Main Setup [200]
Section 11-2
When the selection Trip is set in menu [231] the VSD trips if this limit is
exceeded.
When the selection Limit is set in menu [231] the VSD reduces the torque if
the integrated value is 95% or closer to the limit, so that the limit cannot be
exceeded.
Note
If it is not possible to reduce the current, the VSD will trip after exceeding
110% of the limit.
Example
In Fig. 65 the thick grey line shows the following example.
•
Menu [232] Mot I
2
t Curr is set to 100%.
1.2 x 100% = 120%
•
Menu [233] Mot I
2
t Time is set to 1000 s.
This means that the VSD will trip or reduce after 1000 s if the current is
1.2 times of 100% nominal motor current.
Only visible if the PTC/PT100 option board is installed. Set the PTC input for
thermal protection of the motor. The motor thermistors (PTC) must comply
with DIN 44081/44082. Please refer to the manual for the PTC/PT100 option
board.
Menu [234] PTC contains functions to enable or disable the PTC input. Here
you can select and activate PTC and/or PT100.
Communication information
Note
PTC option and PT100 selections can only be selected in menu [234] if the
option board is mounted.
Note
If you select the PTC option, the PT100 inputs are ignored
Default:
Off
Off
0
PTC and PT100 motor protection are disabled.
PTC 1
Enables the PTC protection of the motor via the insulated
option board.
PT100
2
Enables the PT100 protection for the motor via the insu-
lated option board.
PTC+PT100
3
Enables the PTC protection as well as the PT100 protec-
tion for the motor via the insulated option board.
Modbus Instance no/
DeviceNet no:
43064
Profibus slot/index
168/223
EtherCAT index (hex)
4bf8
Fieldbus format
UInt
Modbus format
UInt
Off
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...