Main Setup [200]
Section 11-2
Only visible if the PTC/PT100 option board is installed. Set the class of motor
used. The trip levels for the PT100 sensor will automatically be set according
to the setting in this menu.
Communication information
Note
This menu is only valid for PT 100.
PT100 Inputs [236]
Sets which of PT100 inputs should be used for thermal protection. Deselect-
ing not used PT100 inputs on the PTC/PT100 option board in order to ignore
those inputs, i.e. extra external wiring is not needed if port is not used.
Communication information
Note
This menu is only valid for PT100 thermal protection if PT100 is enabled in
menu [234].
Default:
F 140
C
A 100
C
0
E 115
C
1
B 120
C
2
F 140
C
3
F Nema 145
C
4
H 165
C
5
Modbus Instance no/
DeviceNet no:
43065
Profibus slot/index
168/224
EtherCAT index (hex)
4bf9
Fieldbus format
UInt
Modbus format
UInt
F 140
C
A
Default:
PT100 1+2+3
Selection:
PT100 1, PT100 2, PT100 1+2, PT100 3, PT100 1+3,
PT100 2+3, PT100 1+2+3
PT100 1
1
Channel 1 used for PT100 protection
PT100 2
2
Channel 2 used for PT100 protection
PT100 1+2
3
Channel 1+2 used for PT100 protection
PT100 3
4
Channel 3 used for PT100 protection
PT100 1+3
5
Channel 1+3 used for PT100 protection
PT100 2+3
6
Channel 2+3 used for PT100 protection
PT100 1+2+3
7
Channel 1+2+3 used for PT100 protection
Modbus Instance no/
DeviceNet no:
43066
Profibus slot/index
168/225
EtherCAT index (hex)
4bfa
Fieldbus format
UInt
Modbus format
UInt
PT100 1+2+3
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...