102
Main Setup [200]
Section 11-2
For VSD sizes B to D there is optional possibility to directly connect motor
PTC (not to be mixed up with PTC/PT100 option board).
In this menu the internal motor PTC hardware option is enabled. This PTC
input complies with DIN 44081/44082. Please refer to the manual for the PTC/
PT100 option board for electrical specification.
This menu is only visible if a PTC (or resistor <2 kOhm) is connected to termi-
nals X1: 78–79. See Chapter 5.4 and Chapter 5.5.1.
Note
This function is not related to PTC/PT100 option board.
To enable the function:
1.
Connect the thermistor wires to X1: 78–79 or for testing the input, connect
a resistor to the terminals. Use resistor value between 50 and 2000 ohm.
Menu [237] will now appear.
2.
Enable input by setting menu [237] Motor PTC=On.
If enabled and <50 ohm a sensor error trip will occur. The fault message
“Motor PTC” is shown.
If the function is disabled and the PTC or resistor is removed, the menu will
disappear after the next power on.
Communication information
Note
This option is only available for SX-D40P7 to SX-D4037
11-2-6 Parameter Set Handling [240]
There are four different parameter sets available in the VSD. These parameter
sets can be used to set the VSD up for different processes or applications
such as different motors used and connected, activated PID controller, differ-
ent ramp time settings, etc.
A parameter set consists of all parameters with the exception of the menu
[211] Language, [217] Local Remote, [218] Lock Code, [220] Motor Data,
[241] Select Set, [260] Serial Communication and [21B] Mains supply voltage.
Note
Actual timers are common for all sets. When a set is changed the timer
functionality will change according to the new set, but the timer value will stay
unchanged.
Here you select the parameter set. Every menu included in the parameter
sets is designated A, B, C or D depending on the active parameter set.
Parameter sets can be selected from the keyboard, via the programmable dig-
ital inputs or via serial communication. Parameter sets can be changed during
Default:
Off
Off
0
Motor PTC protection is disabled
On
1
Motor PTC protection is enabled
Modbus Instance no/
DeviceNet no:
43067
Profibus slot/index
168/226
EtherCAT index (hex)
4bfb
Fieldbus format
UInt
Modbus format
UInt
237 Motor PTC
Stp
Off
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...