113
Main Setup [200]
Section 11-2
Communication information
External Trip [25G]
Delay time starts counting when the fault is gone. When the time delay has
elapsed, the alarm will be reset if the function is active.
Communication information
External Trip Type [25H]
Select the preferred way to react to an alarm trip.
Communication information
Delay time starts counting when the fault is gone. When the time delay has
elapsed, the alarm will be reset if the function is active.
Modbus Instance no/
DeviceNet no:
43085
Profibus slot/index
168/244
EtherCAT index (hex)
4c0d
Fieldbus format
UInt
Modbus format
UInt
Default:
Off
Off
0
Off
1–3600
1–
3600
1–3600 s
Modbus Instance no/
DeviceNet no:
43080
Profibus slot/index
168/239
EtherCAT index (hex)
4c08
Fieldbus format
Long, 1=1 s
Modbus format
EInt
Default:
Trip
Selection:
Same as menu [25B]
Modbus Instance no/
DeviceNet no:
43081
Profibus slot/index
168/240
EtherCAT index (hex)
4c09
Fieldbus format
UInt
Modbus format
UInt
Default:
Off
25G Ext Trip
Stp
Off
A
Trip
A
Off
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...