121
Main Setup [200]
Section 11-2
Note
Menu [214] and/or [215] must be set to COM to activate the communication
fault function.
Communication information
Communication Fault Time [2642]]
Defines the delay time for the trip/warning.
Communication information
Trip
1
RS232/485 selected:
The VSD will trip if there is no communication for time set in
parameter [2642].
Fieldbus selected:
The VSD will trip if:
1. The internal communication between the control board
and fieldbus option is lost for time set in parameter [2642].
2. If a serious network error has occurred.
Warning
2
RS232/485 selected:
The VSD will give a warning if there is no communication
for time set in parameter [2642].
Fieldbus selected:
The VSD will give a warning if:
1. The internal communication between the control board
and fieldbus option is lost for time set in parameter [2642].
2. If a serious network error has occurred.
Modbus Instance no/
DeviceNet no:
43037
Profibus slot/index
168/196
EtherCAT index (hex)
4bdd
Fieldbus format
UInt
Modbus format
UInt
Default:
0.5 s
Range:
0.1-15 s
Modbus Instance no/
DeviceNet no:
43038
Profibus slot/index
168/197
EtherCAT index (hex)
4bde
Fieldbus format
Long, 1=0.1 s
Modbus format
EInt
0.5s
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...