123
Process and Application Parameters [300]
Section 11-3
Communication information
Sub menus showing status of fieldbus parameters. Please see the Fieldbus
manual for detailed information.
11-3 Process and Application Parameters [300]
These parameters are mainly adjusted to obtain optimum process or machine
performance.
The read-out, references and actual values depends on selected process
source, [321}:
11-3-1 Set/View Reference Value [310]
View reference value
As default the menu [310] is in view operation. The value of the active refer-
ence signal is displayed. The value is displayed according to selected process
source, [321] or the process unit selected in menu [322].
Set reference value
If the function Reference Control [214] is set to: Ref Control = Keyboard, the
reference value can be set in menu Set/View Reference [310] as a normal
parameter or as a motor potentiometer with the + and - keys on the control
panel depending on the selection of Keyboard Reference Mode in menu
[369]. The ramp times used for setting the reference value with the Normal
function selected in menu [369] are according to the set Acc Time [331] and
Dec Time [332]. The ramp times used for setting the reference value with the
MotPot function selected in [369] are according to the set Acc MotPot [333]
and Dec MotPot [334]. Menu [310] displays on-line the actual reference value
according to the Mode Settings in Table 24.
Modbus Instance no/
DeviceNet no:
42801-42816
Profibus slot/index
167/215-167/230
EtherCAT index (hex)
4af1-4b00
Fieldbus format
UInt
Modbus format
UInt
Table 24
Selected process
source
Unit for reference and actual
value
Resolution
Speed
rpm
4 digits
Torque
%
3 digits
PT100
C
3 digits
Frequency
Hz
3 digits
Default:
0 rpm
Dependent on:
Process Source [321] and Process Unit [322]
Speed mode
0 - max speed [343]
0rpm
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...