124
Process and Application Parameters [300]
Section 11-3
Communication information
Note
The actual value in menu [310] is not copied, or loaded from the control panel
memory when Copy Set [242], Copy to CP [244] or Load from CP [245] is
performed.
Note
If the MotPot function is used, the reference value ramp times are according to
the Acc MotPot [333] and Dec MotPot [334] settings. Actual speed ramp will
be limited according to Acc Time [331] and Dec Time [332].
Note
Write access to this parameter is only allowed when menu“Ref Control [214]
is set to Keyboard. When Reference control is used, see section 10.5
Reference signal.
11-3-2 Process Settings [320]
With these functions, the VSD can be set up to fit the application. The menus
[110], [120], [310], [362]-[368] and [711] use the process unit selected in [321]
and [322] for the application, e.g. rpm, bar or m3/h. This makes it possible to
easily set up the VSD for the required process requirements, as well as for
copying the range of a feedback sensor to set up the Process Value Minimum
and Maximum in order to establish accurate actual process information.
Select the signal source for the process value that controls the motor. The
Process Source can be set to act as a function of the process signal on AnIn
F(AnIn), a function of the motor speed F(Speed), a function of the shaft torque
F(Torque) or as a function of a process value from serial communication
F(Bus). The right function to select depends on the characteristics and behav-
iour of the process. If the selection Speed, Torque or Frequency is set, the
VSD will use speed, torque or frequency as reference value.
Example
An axial fan is speed-controlled and there is no feedback signal available. The
process needs to be controlled within fixed process values in “m
3
/hr” and a
process read-out of the air flow is needed. The characteristic of this fan is that
the air flow is linearly related to the actual speed. So by selecting F(Speed) as
the Process Source, the process can easily be controlled.
The selection F(xx) indicates that a process unit and scaling is needed, set in
menus [322]-[328]. This makes it possible to e.g. use pressure sensors to
measure flow etc. If F(AnIn) is selected, the source is automatically connected
to the AnIn which has Process Value as selected.
Torque mode
0 - max torque [351]
Other modes
Min according to menu [324] - max according to menu [325]
Modbus Instance no/
DeviceNet no:
42991
Profibus slot/index
168/150
EtherCAT index (hex)
4baf
Fieldbus format
Long
Modbus format
EInt
Default:
Speed
F(AnIn)
0
Function of analogue input. E.g. via PID control, [330].
Speed
1
Speed as process reference
1
.
Speed
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...