Process and Application Parameters [300]
Section 11-3
Deceleration Ramp Type [338]
Sets the ramp type of all deceleration parameters in a parameter set Fig. 72.
Communication information
Fig. 72
Shape of deceleration ramp
Start Mode [339]
Sets the way of starting the motor when a run command is given.
Communication information
Default:
Linear
Selection:
Same as menu [337]
Modbus Instance no/
DeviceNet no:
43108
Profibus slot/index
169/12
EtherCAT index (hex)
4c24
Fieldbus format
UInt
Modbus format
UInt
Default:
Normal DC
Fast
0
The motor shaft flux increases gradually. The motor shaft
starts rotating immediately once the Run command is
given.
Normal DC
1
After a Run command the motor will be magnetised first
and the stator resistance is measured
.
Depending on the
motor time constant and the size of the motor it can take up
to 1.3 s before the motor shaft starts to rotate.
This will pro-
vide better control of the motor when starting.
Modbus Instance no/
DeviceNet no:
43109
Profibus slot/index
169/13
EtherCAT index (hex)
4c25
Fieldbus format
UInt
Modbus format
UInt
338 Dec Rmp
Stp
Linear
A
t
Linear
S-curve
339 Start Mode
Stp Normal DC
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...