142
Process and Application Parameters [300]
Section 11-3
Note
Release torque [33I] has priority over torque reference initialization by
Release Speed [33D].
Fig. 74
Principle of brake operation for fault during run and during stop
11-3-5 Speed [340]
Menu with all parameters for settings regarding to speeds, such as Min/Max
speeds, Jog speeds, Skip speeds.
Minimum Speed [341]
Sets the minimum speed. The minimum speed will operate as an absolute
lower limit. Used to ensure the motor does not run below a certain speed and
to maintain a certain performance.
Note
A lower speed value than the set minimum speed can be shown in the display
due to motor slip.
Communication information
Brake warning
Brake Trip
Brake acknowledge
Brake relay
Speed>0
Torque
Running
Start
During run
During stop
Brake
<33H
33H
<33H
Brake
Brake wait
time
Brake engage
time
33F
33E
33C
33C
release time
release time
Brake Fault trip time
*
**
*
Memorized load torque level, if function activated with parameter [33I] Release Torque
**
Time for operator to set down the load
Default:
0 rpm
Range:
0 - Max Speed
Dependent on:
Set/View ref [310]
Speed
Stp
0rpm
A
Modbus Instance no/
DeviceNet no:
43121
Profibus slot/index
169/25
EtherCAT index (hex)
4c31
Fieldbus format
Int, 1=1 rpm
Modbus format
Int, 1=1 rpm
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...