146
Process and Application Parameters [300]
Section 11-3
The same function as menu [345] for the 2nd skip range.
Communication information
The Jog Speed function is activated by one of the digital inputs. The digital
input must be set to the Jog function [520]. The Jog command/function will
automatically generate a run command as long as the Jog command/function
is active. The rotation is determined by the polarity of the set Jog Speed.
Example
If Jog Speed = -10, this will give a Run Left command at
10 rpm regardless of RunL or RunR commands. Fig. 77 shows the function of
the Jog command/function.
Communication information
Default:
0 rpm
Range:
0 – 4 x Motor Sync Speed
Modbus Instance no/
DeviceNet no:
43127
Profibus slot/index
169/31
EtherCAT index (hex)
4c37
Fieldbus format
Int, 1=1 rpm
Modbus format
Int, 1=1 rpm
Default:
50 rpm
Range:
-4 x motor sync speed to +4 x motor sync speed
Dependent on:
Defined motor sync speed. Max = 400%, normally
max=VSD I
max
/motor I
nom
x 100%.
Modbus Instance no/
DeviceNet no:
43128
Profibus slot/index
169/32
EtherCAT index (hex)
4c38
Fieldbus format
Int
Modbus format
Int
0rpm
A
50rpm
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...