Process and Application Parameters [300]
Section 11-3
Selecting “Automatic” will use the optimal value according to the internal
model of motor. “User-Defined” can be selected when the start conditions of
the application do not change and a high starting torque is always required. A
fixed IxR Compensation value can be set in the menu [353].
Note
This menu is visible only in V/Hz mode.
Communication information
Fig. 78
IxR Comp at Linear V/Hz curve
Only visible if User-Defined is selected in previous menu.
Communication information
Default:
Off
Off
0
Function disabled
Automatic
1
Automatic compensation
User Defined
2
User defined value in percent.
352 IxR Comp
Stp
Off
A
Modbus Instance no/
DeviceNet no:
43142
Profibus slot/index
169/46
EtherCAT index (hex)
4c46
Fieldbus format
UInt
Modbus format
UInt
Default:
0.0%
Range:
0-25% x U
NOM
(0.1% of resolution)
Modbus Instance no/
DeviceNet no:
43143
Profibus slot/index
169/47
EtherCAT index (hex)
4c47
Fieldbus format
Long
Modbus format
EInt
10
20
30
40
50 Hz
f
25
%
U
100
IxR Comp=25%
IxR Com=0%
0.0%
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...