153
Process and Application Parameters [300]
Section 11-3
Speed PI Autotune [371]
The function speed autotune will perform a torque step change, and mea-
sures the reaction on shaft speed.
It automatically sets the internal speed I time to its optimum value. The speed
PI autotune must be done during operation with the motor load connected and
the motor running. “Spd PI Auto” will be blinking in the display during the auto-
tune operation. When the test is successfully concluded, the display will show
“Spd PI OK!” for 3 s.
Communication information
Note
Run the autotune at speed lower than 80% of the nominal motor speed.
Otherwise autotune will fail.
Note
The setting will automatically return to Off when the autotuning is finished.
Note
This menu is only visible if VSD Mode = Speed or V/Hz.
For adjusting the P gain of the internal speed controller. The speed P gain
must be manually tuned for a faster reaction to load changes. The speed P
gain can be increased until there is audible noise from the motor and then
decreased until the noise disappears.
Communication information
Default:
Off
Off
0
On
1
Modbus Instance no/
DeviceNet no:
43151
Profibus slot/index
169/55
EtherCAT index (hex)
4c4f
Fieldbus format
UInt
Modbus format
UInt
Off
A
Default:
See note
Range:
0.0–60.0
Modbus Instance no/
DeviceNet no:
43152
Profibus slot/index
169/56
EtherCAT index (hex)
4c50
Fieldbus format
Long, 1=0.1
Modbus format
EInt
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...