155
Process and Application Parameters [300]
Section 11-3
Setting the P gain for the PID controller.
Communication information
Fig. 81
Closed loop PID control
Setting the integration time for the PID controller.
Communication information
Setting the differentiation time for the PID controller.
Default:
1.0
Range:
0.0–30.0
Modbus Instance no/
DeviceNet no:
43156
Profibus slot/index
169/60
EtherCAT index (hex)
4c54
Fieldbus format
Long, 1=0.1
Modbus format
EInt
Default:
1.00 s
Range:
0.01–300 s
Modbus Instance no/
DeviceNet no:
43157
Profibus slot/index
169/61
EtherCAT index (hex)
4c55
Fieldbus format
Long, 1=0.01 s
Modbus format
EInt
Default:
0.00 s
Range:
0.00–30 s
1.0
A
+
M
-
06-F95
Process
reference
Process
feedback
Process
PID
VSD
Process
1.00s
A
0.00s
A