161
Process and Application Parameters [300]
Section 11-3
the digital inputs are also used for status feedback, these must be set for the
pump control according to; Pump 1 OK– Pump6 OK in menu
[520].
Note
Used relays must be defined as Slave Pump or Master Pump. Used digital
inputs must be defined as Pump Feedback.
Communication information
Select Drive [393]
Sets the main operation of the pump system. 'Sequence' and 'Runtime' are
Fixed MASTER operation. 'All' means Alternating MASTER operation.
Default:
1
1-3
Number of drives if I/O Board is not used.
1-6
Number of drives if 'Alternating MASTER' is used, see
Select Drive [393]. (I/O Board is used.)
1-7
Number of drives if 'Fixed MASTER' is used, see Select
Drive [393].
(I/O Board is used.)
A
1
Modbus Instance no/
DeviceNet no:
43162
Profibus slot/index
169/66
EtherCAT index (hex)
4c5a
Fieldbus format
UInt
Modbus format
UInt
Default:
Sequence
Sequence
0
Fixed MASTER operation:
- The additional drives will be selected in sequence, i.e. first
pump 1 then pump 2 etc.
- A maximum of 7 drives can be used.
Run Time
1
Fixed MASTER operation:
- The additional drives will be selected depending on the
Run Time. So the drive with the lowest Run Time will be
selected first. The Run Time is monitored in menus [39H] to
[39M] in sequence. For each drive the Run Time can be
reset.
- When drives are stopped, the drive with the longest Run
Time will be stopped first.
- Maximum 7 drives can be used.
All
2
Alternating MASTER operation:
- When the drive is powered up, one drive is selected as the
Master drive. The selection criteria depends on the Change
Condition [394]. The drive will be selected according to the
Run Time. So the drive with the lowest Run Time will be
selected first. The Run Time is monitored in menus [39H] to
[39M] in sequence. For each drive the Run Time can be
reset.
- A maximum of 6 drives can be used.
Sequence
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...