163
Process and Application Parameters [300]
Section 11-3
When the time set here is elapsed, the master drive will be changed. This
function is only active if Select Drive [393]=All and Change Cond [394]=
Timer/ Both.
Communication information
If a master drive is changed according to the timer function (Change Condi-
tion=Timer/Both [394]), it is possible to leave additional pumps running during
the change operation. With this function the change operation will be as
smooth as possible. The maximum number to be programmed in this menu
depends on the number of additional drives.
Example:
If the number of drives is set to 6, the maximum value will be 4. This function
is only active if Select Drive [393]=All.
Communication information
If the speed of the master drive comes into the upper band, an additional drive
will be added after a delay time that is set in start delay [399].
Default:
50 h
Range:
1-3000 h
Modbus Instance no/
DeviceNet no:
43165
Profibus slot/index
169/69
EtherCAT index (hex)
4c5d
Fieldbus format
UInt, 1=1 h
Modbus format
UInt, 1=1 h
Default:
0
Range:
0 to (the number of drives - 2)
Modbus Instance no/
DeviceNet no:
43166
Profibus slot/index
169/70
EtherCAT index (hex)
4c5e
Fieldbus format
UInt
Modbus format
UInt
Default:
10%
Range:
0-100% of total min speed to max speed
50h
A
A
0
10%
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...