165
Process and Application Parameters [300]
Section 11-3
Stop delay will be activated:
Range = Max Speed - Min Speed = 1500–300 = 1200 rpm
10% of 1200 rpm = 120 rpm
Start level = 300 + 120 = 420 rpm
Fig. 86
Lower band
Start Delay [399]
This delay time must have elapsed before the next pump is started. A delay
time prevents the nervous switching of pumps.
Communication information
Stop Delay [39A]
This delay time must have elapsed before the 'top' pump is stopped. A delay
time prevents the nervous switching of pumps.
Communication information
Default:
0 s
Range:
0-999 s
Modbus Instance no/
DeviceNet no:
43169
Profibus slot/index
169/73
EtherCAT index (hex)
4c61
Fieldbus format
Long, 1=1s
Modbus format
EInt
Default:
0 s
Range:
0-999 s
Modbus Instance no/
DeviceNet no:
43170
Profibus slot/index
169/74
EtherCAT index (hex)
4c62
Fieldbus format
Long, 1=1 s
Modbus format
EInt
(NG_50-PC-13_1)
Speed
Max
Min
“top” pump stops
Lower band
Stop Delay [39A]
Flow/Pressure
0s
A
0s
A