172
Process and Application Parameters [300]
Section 11-3
Note
This menu is only visible if the crane board is connected to the VSD.
Crane enable [3A1]
When the crane option board is connected, it is possible to (de)activate the
crane option board inputs.
Note
Deviation function is active even if [3A1]=off.
Communication information
To select the type of crane joystick control.
Communication information
Crane Relay CR1 [3A3]
Crane Relay CR1 on the Crane option board is fixed to the No Trip function.
Communication information
Default:
Off
Off
0
Crane option board deactivated
On
1
Crane option board activated
On
A
Modbus Instance no/
DeviceNet no:
43181
Profibus slot/index
169/85
EtherCAT index (hex)
4c6d
Fieldbus format
UInt
Modbus format
UInt
Default:
4-Speeds
4-Speeds
0
4-Speed joystick
3-Pos
1
3-Position switch
Analogue
2
Analogue joystick
Modbus Instance no/
DeviceNet no:
43182
Profibus slot/index
169/86
EtherCAT index (hex)
4c6e
Fieldbus format
UInt
Modbus format
UInt
Default:
No Trip
Selections
Fixed to No Trip
Modbus Instance no/
DeviceNet no:
43183
Profibus slot/index
169/87
3A2 Control
Stp
4-Speeds
A
No Trip
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...