173
Process and Application Parameters [300]
Section 11-3
Crane Relay CR2 [3A4]
To select the function of Crane Relay CR2 on the Crane option board. Same
selections as for the relays on the control board.
Communication information
To set the speed used when Pre-Limit Switch on the Crane option board is
active.
Communication information
To set the speed used when crawling (min. speed) during a hoisting operation.
Activated with input A1, Crawl H/R=Start in positive speed direction
Communication information
EtherCAT index (hex)
4c6f
Fieldbus format
UInt
Modbus format
UInt
Default:
Brake
Selections
Same selections as for the relays on the control board
Modbus Instance no/
DeviceNet no:
43184
Profibus slot/index
169/88
EtherCAT index (hex)
4c70
Fieldbus format
UInt
Modbus format
UInt
Default:
0 rpm
Range:
0 – 4 x Motor Sync speed
Modbus Instance no/
DeviceNet no:
43185
Profibus slot/index
169/89
EtherCAT index (hex)
4c71
Fieldbus format
Int, 1=1 rpm
Modbus format
Int, 1=1 rpm
Default:
0
Range:
0 – 4 x Sync speed
Modbus Instance no/
DeviceNet no:
43189
Profibus slot/index
169/93
EtherCAT index (hex)
4c75
Brake
A
rpm
A
rpm
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...