181
Load Monitor and Process Protection [400]
Section 11-4
Min Pre Alarm [418]
Min Pre Alarm Margin [4181]
With load type Basic, [415], used the Min Pre-Alarm Margin sets the band
under the Normal Load, [41B], menu that does not generate a pre-alarm. With
load type Load Curve, [415], used the Min Pre-Alarm Margin sets the band
under the Load Curve, [41C], that does not generate a pre-alarm. The Min
Pre-Alarm Margin is a percentage of nominal motor torque.
Communication information
Min Pre Alarm Response delay [4182]
When the load level without interruption is below the alarm level longer than
set “Min PreAlarm delay” time, a warning is activated.
Communication information
Min Alarm [419]
Min Alarm Margin [4191]
With load type Basic, [415], used the Min Alarm Margin sets the band under
the Normal Load, [41B], menu that does not generate an alarm. With load
type Load Curve, [415], used the Min Alarm Margin sets the band under the
Load Curve, [41C], that does not generate an alarm. The Max Alarm Margin is
a percentage of nominal motor torque.
Fieldbus format
Long, 1=0.1 s
Modbus format
EInt
Default:
10%
Range:
0-400%
Modbus Instance no/
DeviceNet no:
43328
Profibus slot/index
169/232
EtherCAT index (hex)
4d00
Fieldbus format
Long, 1=1%
Modbus format
EInt
Default:
0.1 s
Range:
0-90 s
Modbus Instance no/
DeviceNet no:
43332
Profibus slot/index
169/236
EtherCAT index (hex)
4d04
Fieldbus format
Long, 1=0.1 s
Modbus format
EInt
10%
A
0.1s
A
15%
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...