182
Load Monitor and Process Protection [400]
Section 11-4
Communication information
Min Alarm Response delay [4192]
When the load level without interruption is below the alarm level longer than
set “Min Alarm delay” time, an alarm is activated.
Communication information
Autoset Alarm [41A]
The Autoset Alarm function can measure the nominal load that is used as ref-
erence for the alarm levels. If the selected Load Type [415] is Basic it copies
the load the motor is running with to the menu Normal Load [41B]. The motor
must run on the speed that generates the load that needs to be recorded. If
the selected Load Type [415] is Load Curve it
performs a test-run and popu-
lates the Load Curve [41C] with the found load values.
!Warning
When autoset does a test run the motor and application/machine will ramp up
to maximum speed.
Note
The motor must be running for the Autoset Alarm function to succeed. A not
running motor generates a “Failed!” message.
Communication information
Default:
15%
Range:
0-400%
Modbus Instance no/
DeviceNet no:
43329
Profibus slot/index
169/233
EtherCAT index (hex)
4d01
Fieldbus format
Long, 1=1%
Modbus format
EInt
Default:
0.1 s
Range:
0-90 s
Modbus Instance no/
DeviceNet no:
43333
Profibus slot/index
169/237
EtherCAT index (hex)
4d05
Fieldbus format
Long, 1=0.1 s
Modbus format
EInt
0.1s
A
Default:
No
No
0
Yes
1
No
A
Modbus Instance no/
DeviceNet no:
43334
Profibus slot/index
169/238
EtherCAT index (hex)
4d06
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...