192
I/Os and Virtual Connections [500]
Section 11-5
selected function. The range is set by changing the positive maximum value;
the negative value is automatically adapted accordingly. Only visible if [512] =
User Bipol mA/V. The inputs RunR and RunL input need to be active, and
Rotation, [219], must be set to “R+L”, to operate the bipolar function on the
analogue input.
Communication information
With AnIn1 Function Min the physical minimum value is scaled to selected
process unit. The default scaling is dependent of the selected function of
AnIn1 [511].
Table 26 shows corresponding values for the min and max selections depend-
ing on the function of the analogue input [511].
Communication information
Default:
0.00–10.00 V
Range:
0.0–20.0 mA, 0.00–10.00 V
Modbus Instance no/
DeviceNet no:
43205
Profibus slot/index
169/109
EtherCAT index (hex)
4c85
Fieldbus format
Long
Modbus format
EInt
Default:
Min
Min
0
Min value
Max
1
Max value
User-defined
2
Define user value in menu [5135]
Table 26
AnIn Function
Min
Max
Speed
Min Speed [341]
Max Speed [343]
Torque
0%
Max Torque [351]
Process Ref
Process Min [324]
Process Max [325]
Process Value
Process Min [324]
Process Max [325]
Modbus Instance no/
DeviceNet no:
43206
Profibus slot/index
169/110
EtherCAT index (hex)
4c86
Fieldbus format
UInt
Modbus format
UInt
10.00V
A
Min
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...