193
I/Os and Virtual Connections [500]
Section 11-5
AnIn1 Function Value Min [5135]
With AnIn1 Function ValMin you define a user-defined value for the signal.
Only visible when user-defined is selected in menu [5134].
Communication information
With AnIn1 Function Max the physical maximum value is scaled to selected
process unit. The default scaling is dependent of the selected function of
AnIn1 [511]. See Table 26.
Communication information
AnIn1 Function Value Max [5137]
With AnIn1 Function VaMax you define a user-defined value for the signal.
Only visible when user-defined is selected in menu [5136].
Default:
0.000
Range:
-10000.000 – 10000.000
Modbus Instance no/
DeviceNet no:
43541
Profibus slot/index
170/190
EtherCAT index (hex)
4dd5
Fieldbus format
Long,
Speed 1=1 rpm
Torque 1=1%
Process val 1=0.001
Modbus format
EInt
Default:
Max
Min
0
Min value
Max
1
Max value
User-defined
2
Define user value in menu [5137]
Modbus Instance no/
DeviceNet no:
43207
Profibus slot/index
169/111
EtherCAT index (hex)
4c87
Fieldbus format
Long,
Speed/Torque 1=1 rpm or %.
Other 1= 0.001
Modbus format
EInt
Default:
0.000
Range:
-10000.000 – 10000.000
0.000
A
Max
A
0.000
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...