200
I/Os and Virtual Connections [500]
Section 11-5
Note
For bipol function, input RunR and RunL needs to be active and Rotation,
[219] must be set to “R+L”.
Communication information
Note
To activate the parameter set selection, menu 241 must be set to DigIn.
Digital Input 2 [522] to Digital Input 8 [528]
Same function as DigIn 1 [521]. Default function for DigIn 8 is Reset. For DigIn
3 to 7 the default function is Off.
Pump5 Feedb
19
Feedback input pump5 for Pump/Fan control and informs
about the status of the auxiliary connected pump/fan.
Pump6 Feedb
20
Feedback input pump 6 for Pump/Fan control and informs
about the status of the auxiliary connected pump/fan.
Timer 1
21
Timer 1 Delay [643] will be activated on the rising edge of
this signal.
Timer 2
22
Timer 2 Delay [653] will be activated on the rising edge of
this signal.
Set Ctrl 1
23
Activates other parameter set. See Table 27 for selection
possibilities.
Set Ctrl 2
24
Activates other parameter set. See Table 27 for selection
possibilities.
Mot PreMag
25
Pre-magnetises the motor. Used for faster motor start.
Jog 26
To activate the Jog function. Gives a Run command with
the set Jog speed and Direction, page 146.
Ext Mot Temp
27
Be aware that if there is nothing connected to the input, the
VSD will trip at “External Motor Temp” immediately.
NOTE: The External Motor Temp is active low.
Loc/Rem
28
Activate local mode defined in [2171] and [2172].
AnIn select
29
Activate/deactivate analogue inputs defined in [513A],
[516A], [519A] and [51CA]
LC Level
30
Liquid cooling low level signal.
NOTE: The Liquid Cooling Level is active low.
Brk Ackn
31
Brake acknowledge input for Brake Fault control. Function
is activated via this selection see menu [33H]
Modbus Instance no/
DeviceNet no:
43241
Profibus slot/index
169/145
EtherCAT index (hex)
4ca9
Fieldbus format
UInt
Modbus format
UInt
Table 27
Parameter Set
Set Ctrl 1
Set Ctrl 2
A
0
0
B
1
0
C
0
1
D
1
1
Default:
RunR
Selection:
Same as in menu
[
]
522 DigIn 2
Stp
RunR
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...