205
I/Os and Virtual Connections [500]
Section 11-5
*) Fmin is dependent on the set value in menu Minimum Speed [341].
Communication information
Example
Set the AnOut function for Motorfrequency to 0Hz, set AnOut functionMin
[5334] to “User-defined” and AnOut1 VaMin[5335] = 0.0. This results in an
analogue output signal from 0/4 mA to 20mA: 0 Hz to Fmot.
This principle is valid for all Min to Max settings.
AnOut1 Function Value Min [5335]
With AnOut1 Function VaMin you define a user-defined value for the signal.
Only visible when user-defined is selected in menu [5334].
Communication information
With AnOut1 Function Min the physical minimum value is scaled to selected
presentation. The default scaling is dependent on the selected function of
AnOut1 [531]. See Table 28.
Communication information
Modbus Instance no/
DeviceNet no:
43256
Profibus slot/index
169/160
EtherCAT index (hex)
4cb8
Fieldbus format
Long,
1=0.1 W, 0.1 Hz, 0.1 A, 0.1 V or 0.001
Modbus format
EInt
Default:
0.000
Range:
-10000.000–10000.000
Modbus Instance no/
DeviceNet no:
43545
Profibus slot/index
170/194
EtherCAT index (hex)
4dd9
Fieldbus format
Long,
Speed 1=1 rpm
Torque 1=1%
Process val 1=0.001
Modbus format
EInt
Default:
Max
Min
0
Min value
Max
1
Max value
User defined
2
Define user value in menu [5337]
Modbus Instance no/
DeviceNet no:
43257
Profibus slot/index
169/161
EtherCAT index (hex)
4cb9
0.000
A
Max
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...