217
Logical Functions and Timers [600]
Section 11-6
Communication information
Example
Create automatic RUN/STOP signal via the analogue reference signal. Ana-
logue current reference signal, 4-20 mA, is connected to Analogue Input 1.
AnIn1 Setup, menu [512] = 4-20 mA and the threshold is 4 mA. Full scale
(100%) input signal on AnIn 1 = 20 mA. When the reference signal on AnIn1
increases 80% of the threshold (4 mA x 0.8 = 3.2 mA), the VSD will be set in
RUN mode. When the signal on AnIn1 goes below 60% of the threshold (4
mA x 0.6 = 2.4 mA) the VSD is set to STOP mode. The output of CA1 is used
as a virtual connection source that controls the virtual connection destination
RUN.
Modbus Instance no/
DeviceNet no:
43401
Profibus slot/index
170/50
EtherCAT index (hex)
4d49
Fieldbus format
UInt
Modbus format
UInt
Menu
Function
Setting
AnIn1 Function
Process reference
AnIn1 Set-up
4-20 mA, threshold is 4 mA
Min Speed
0
Max Speed
1500
6111
CA1 Value
AnIn1
6112
CA1 Level HI
16% (3.2mA/20mA x 100%)
6113
CA1 Level LO
12% (2.4mA/20mA x 100%)
6114
CA1 Type
Hysteresis
VIO 1 Dest
RunR
VIO 1 Source
CA1
Run/Stp Ctrl
Remote
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...