219
Logical Functions and Timers [600]
Section 11-6
Note
If bipolar is selected [6115] then Min value is equal to -Max in the table
Communication information
Example
This example describes the normal use of the constant level high and low.
Shaft Power, kW
0
Motor P
n
x4
0
El Power, kW
0
Motor P
n
x4
0
Current, A
0
Motor I
n
x4
1
Output volt, V
0
1000
1
Frequency, Hz
0
400
1
DC voltage, V
0
1250
1
Heatsink temp,
C
0
100
1
PT 100_1_2_3,
C
-100
300
1
Energy, kWh
0
1000000
0
Run time, h
0
65535
0
Mains time, h
0
65535
0
AnIn 1-4%
0
100
0
Process Ref
Set by process settings [321] and [322]
3
Process Err
Mode
Min
Max
Decimals
Modbus Instance no/
DeviceNet no:
43402
Profibus slot/index
170/51
EtherCAT index (hex)
4d4a
Fieldbus format
Long,
1=1 W, 0.1 A, 0.1 V,
0.1 Hz, 0.1
C, 1 kWh, 1H, 1%, 1 rpm or 0.001 via process
value
Modbus format
EInt
Menu
Function
Setting
Max Speed
1500
6111
CA1 Value
Speed
6112
CA1 Level HI
300 rpm
6113
CA1 Level LO
200 rpm
6114
CA1 Type
Hysteresis
VC1 Dest
Timer 1
VC1 Source
CA1
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...