236
Logical Functions and Timers [600]
Section 11-6
Timer 1 Trig [641]
Communication information
Communication information
Timer 1 Delay [643]
This menu is only visible when timer mode is set to delay.
This menu can only be edited as in alternative 2, see section 9-5, page 75.
Timer 1 delay sets the time that will be used by the first timer after it is acti-
vated. Timer 1 can be activated by a high signal on a DigIn that is set to Timer
1 or via a virtual destination [560].
Communication information
Default:
Off
Selection:
Same selections as Digital Output 1 menu [541].
Modbus Instance no/
DeviceNet no:
43431
Profibus slot/index
170/80
EtherCAT index (hex)
4d67
Fieldbus format
UInt
Modbus format
UInt
Default:
Off
Off
0
Delay
1
Alternate
2
Modbus Instance no/
DeviceNet no:
43432
Profibus slot/index
170/81
EtherCAT index (hex)
4d68
Fieldbus format
UInt
Modbus format
UInt
Default:
0:00:00 (hr:min:sec)
Range:
0:00:00–9:59:59
Modbus Instance no/
DeviceNet no:q
43433 hours
43434 minutes
43435 seconds
Profibus slot/index
170/82, 170/83,
170/84
EtherCAT index (hex)
4d69 hours
4d6a minutes
4d6b seconds
Off
A
Off
A
0:00:00
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...