View Operation/Status [700]
Section 11-7
1: DigOut1
2: DigOut2
The status of the associated output is shown.
1: High
0: Low
The example in Fig. 112 indicates that DigOut1 is active and Digital Out 2
is
not active.
Relay 1 is active, relay 2 and 3 are not active.
Fig. 112 Digital output status example
Communication information
Analogue Input Status [725]
Indicates the status of the analogue inputs 1 and 2.
Fig. 113 Analogue input status
Communication information
The first row indicates the analogue inputs.
1: AnIn 1
2: AnIn 2
Reading downwards from the first row to the second row the status of the
belonging input is shown in %:
-100% AnIn1 has a negative 100% input value
65% AnIn2 has a 65% input value
So the example in Fig. 113 indicates that both the Analogue inputs are active.
Note
The shown percentages are absolute values based on the full range/scale of
the in- our output; so related to either 0–10 V or 0–20 mA.
Modbus Instance no/
DeviceNet no:
31018
Profibus slot/index
121/162
EtherCAT index (hex)
23fa
Fieldbus format
UInt, bit 0=DigOut1,
bit 1=DigOut2
bit 8=Relay1
bit 9=Relay2
bit 10=Relay3
Modbus format
Modbus Instance no/
DeviceNet no:
31019, 31020
Profibus slot/index
121/163, 121/164
EtherCAT index (hex)
23fb, 23fc
Fieldbus format
Long, 1=1%
Modbus format
EInt
724 DigOutStatus
Stp RE 100 DO 10
2
Stp
-100% 65%
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...