21
Cabinet mounting
Section 2-3
2-3
Cabinet mounting
2-3-1
Cooling
If the variable speed drive is installed in a cabinet, the rate of airflow supplied
by the cooling fans must be taken into consideration.
Note
For the models 4450-4500 and 6800-61K0 the mentioned amount of air flow
should be divided equally over the two cabinets.
2-3-2
Recommended free space in front of cabinet
All cabinet mounted AC drives are designed in modules, so called PEBBs.
These PEBBs can be folded out to be replaced. To be able to remove a PEBB
in the future, we recommend 1.30 meter free in front of the cabinet, see next
figure for details.
Fig. 16 Recommended free space in front of the cabinet mounted AC drive
Table 5
Flow rates cooling fans
Frame
SX-F Model
Flow rate [m
3
/hour]
B
40P7 - 47P5
75
C
4011 - 4015
120
c
4018 - 4022
170
D
4030 - 4037
175
E
4045 - 4090
510
F 4110
-
4132
800
F69
6090 - 6160
G
4160 - 4200
1020
H
4220 - 4250
1600
H69
6200 - 6355
I
4315 - 4400
2400
I69
6450 - 6500
J
4450 - 4500
3200
J69
6600 - 6630
K
4630 - 4800
4800
K69
6710 - 61K0
RIT
TA
L
RIT
TA
L
RIT
TA
L
RIT
TA
L
RIT
TA
L
RIT
TA
L
1300
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...