27
Cable connections
Section 3-2
Note
The Brake and DC-link Terminals are only fitted if the Brake Chopper Option is
built-in.
!Warning
The Brake Resistor must be connected between terminals DC+ and R.
!Warning
In order to work safely, the mains earth must be connected to PE and the
motor earth to
.
3-2-2
Motor cables
To comply with the EMC emission standards the variable speed drive is pro-
vided with a RFI mains filter. The motor cables must also be screened and
connected on both sides. In this way a so-called “Faraday cage” is created
around the VSD, motor cables and motor. The RFI currents are now fed back
to their source (the IGBTs) so the system stays within the emission levels.
Recommendations for selecting motor cables
•
Use screened cables according to specification in table 7. Use symmetri-
cal shielded cable; three phase conductors and a concentric or otherwise
symmetrically constructed PE conductor, and a shield.
•
PE conductor cross-sectional are shall for cable size
16mm
2
be equal to
the used phase conductors, for cable size above 16mm
2
but smaller or
equal to 35mm
2
the PE conductor cross-sectional area shall be at least
16mm
2
. For cables > 35mm
2
the PE conductor cross-sectional area
should be at least 50% of the used phase conductor.
•
When the PE conductor in the used cable type is not in accordance with
the above mentioned cross-sectional area requirements, a separate PE
conductor should be used to establish this.
•
When the conductivity of the cable PE conductor is <50% of the conductiv-
ity of the phase conductor, a separate PE conductor is required.
•
Use heat-resistant cables, +60
C or higher.
•
Dimension the cables and fuses in accordance with the nominal output
current of the motor. See table 48, page 282.
•
Keep the motor cable between VSD and motor as short as possible.
•
The screening must be connected with a large contact surface of prefera-
ble 360
and always at both ends, to the motor housing and the VSD hous-
ing. When painted mounting plates are used, do not be afraid to scrape
away the paint to obtain as large contact surface as possible at all mount-
ing points for items such as saddles and the bare cable screening. Relying
just on the connection made by the screw thread is not sufficient.
Note
It is important that the motor housing has the same earth potential as the
other parts of the machine.
•
The litz ground connection, see fig. 26, is only necessary if the mounting
plate is painted. All the variable speed drives have an unpainted back side
and are therefore suitable for mounting on an unpainted mounting plate.
Connect the motor cables according to U - U, V - V and W - W.
Note
The terminals DC-, DC+ and R are options.
Switches between the motor and the VSD
If the motor cables are to be interrupted by maintenance switches, output
coils, etc., it is necessary that the screening is continued by using metal hous-
ing, metal mounting plates, etc. as shown in the Fig. 25.
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...