29
Cable connections
Section 3-2
Fig. 25 Variable speed drive in a cabinet on a mounting plate
Fig. 26 shows an example when there is no metal mounting plate used (e.g. if
IP54 variable speed drives are used). It is important to keep the “circuit”
closed, by using metal housing and cable glands.
Fig. 26 Variable speed drive as stand alone
VSD built into cabinet
VSD
RFI-Filter
(option)
Mains
Metal EMC cable glands
Output coil (option)
Screened cables
Unpainted mounting plate
Metal connector housing
Motor
Metal EMC
coupling nut
Brake resistor
(option)
Mains
(L1,L2,L3,PE)
Litz
Motor
VSD
RFI-Filter
Mains
Metal EMC cable glands
Screened cables
Metal housing
Brake
resistor
(option)
Output
coils
(option)
Metal connector housing
Motor
Metal cable gland
Mains