Cable specifications
Section 3-4
3-4
Cable specifications
3-5
Stripping lengths
Fig. 31 indicates the recommended stripping lengths for motor and mains
cables.
Fig. 31 Stripping lengths for cables
3-5-1
Dimension of cables and fuses
Please refer to the chapter Technical data, section 14-6, page 282.
3-5-2
Tightening torque for mains and motor cables
Table 7
Cable specifications
Cable
Cable specification
Mains
Power cable suitable for fixed installation for the voltage used.
Motor
Symmetrical three conductor cable with concentric protection (PE) wire or a four con-
ductor cable with compact low-impedance concentric shield for the voltage used.
Control
Control cable with low-impedance shield, screened.
Table 8
Stripping lengths for mains and motor cables
Model
Mains cable
Motor cable
a (mm)
b (mm)
a (mm)
b (mm)
c (mm)
SX-D40P7-EF to SX-D47P5-EF
90
10
90
10
20
SX-D4011-EF to SX-D4022-EF
150
14
150
14
20
SX-D4030-EF to SX-D4037-EF
110
17
110
17
34
SX-D4045-EF to SX-D4090-EF
160
16
160
16
41
SX-D4110-EFto SX-D4132-EF
SX-D6090-EFto SX-D6160-EF
170
24
170
24
46
(06-F45-cables only)
Motor
Mains
Table 9
Model SX-D40P7-EF to SX-D4022-EF
Brake chopper
Mains/motor
Tightening torque, Nm
1.2 - 1.4
1.2 - 1.4
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...