40
Local control
Section 4-4
13. Switch off power supply.
14. Connect digital and analogue inputs/outputs as in Fig. 34.
15. Ready!
16. Switch on power supply.
4-3-4
Run the VSD
Now the installation is finished, and you can press the external start button to
start the motor.
When the motor is running the main connections are OK.
4-4
Local control
Manual control via the control panel can be used to carry out a test run.
Use a 400 V motor and the control panel.
4-4-1
Switch on the mains
Once the mains is switched on, the VSD is started and the internal fan will run
for 5 seconds.
4-4-2
Select manual control
Menu [100], Preferred View is displayed when started.
1.
Press
to display menu [200], Main Setup.
2.
Press
to display menu [210], Operation.
3.
Press
to display menu [211], Language.
4.
Press
to display menu [214], Reference Control.
5.
Select Keyboard using the key
and press
to confirm.
6.
Press
to get to menu [215], Run/Stop Control.
7.
Select Keyboard using the key
and press
to confirm.
8.
Press
to get to previous menu level and then
to display menu [220],
Motor Data.
4-4-3
Set the Motor Data
Enter correct motor data for the connected motor.
9.
Press
to display menu [221].
10. Change the value using the
and
keys. Confirm with
.
11. Press
to display menu [222].
12. Repeat step 9 and 10 until all motor data is entered.
13. Press
twice and then
to display menu [100], Preferred View.
4-4-4
Enter a Reference Value
Enter a reference value.
14. Press
until menu [300], Process is displayed.
15. Press
to display menu [310], Set/View reference value.
16. Use the
and
keys to enter, for example, 300 rpm. We select a low
value to check the rotation direction without damaging the application.
4-4-5
Run the VSD
Press the
key on the control panel to run the motor forward.
If the motor is running the main connections are OK.
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...