42
Terminal connections
Section 5-2
5-2
Terminal connections
The terminal strip for connecting the control signals is accessible after open-
ing the front panel.
The table describes the default functions for the signals. The inputs and out-
puts are programmable for other functions as described in chapter SECTION
11 page 83. For signal specifications refer to chapter SECTION 14 page 277.
Note
The maximum total combined current for outputs 11, 20 and 21 is 100mA.
Table 16 Control signals
Terminal
Name
Function (Default)
Outputs
1
+10 V
+10 VDC supply voltage
6
-10 V
-10 VDC supply voltage
7
Common
Signal ground
11
+24 V
+24 VDC supply voltage
12
Common
Signal ground
15
Common
Signal ground
Digital inputs
8
DigIn 1
RunL (reverse)
9
DigIn 2
RunR (forward)
10
DigIn 3
Off
16
DigIn 4
Off
17
DigIn 5
Off
18
DigIn 6
Off
19
DigIn 7
Off
22
DigIn 8
RESET
Digital outputs
20
DigOut 1
Ready
21
DigOut 2
Brake
Analogue inputs
2
AnIn 1
Process Ref
3
AnIn 2
Off
4
AnIn 3
Off
5
AnIn 4
Off
Analogue outputs
13
AnOut1
Min speed to max speed
14
AnOut2
0 to max torque
Relay outputs
31
N/C 1
Relay 1 output
Trip, active when the VSD is in a TRIP condition.
32
COM 1
33
N/O 1
41
N/C 2
Relay 2 output
Run, active when the VSD is started.
42
COM 2
43
N/O 2
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...