v
WARNINGS AND CAUTIONS
Safety Instructions
Condensation
If the variable speed drive is moved from a cold (storage) room to a room where it will be
installed, condensation can occur. This can result in sensitive components becoming damp. Do
not connect the mains voltage until all visible dampness has evaporated.
Grounding the inverter
Be sure to ground the unit. Not doing so may result in a serious injury due to an electric shock or
fire.
Power factor capacitors for improving cos
Remove all capacitors from the motor and the motor outlet.
Incorrect connection
The variable speed drive is not protected against incorrect connection of the mains voltage, and
in particular against connection of the mains voltage to the motor outlets U, V and W. The vari-
able speed drive can be damaged in this way.
Stop motion mechanical device to ensure safety
The inverter controls the motor electrically, but has no means to stop it mechanically under some
types of failures... In applications where mechanical stop is required to a degree of safety, a
safety assurance study should be carried out to determine the need of additional mechanical
braking devices.
Braking resistor and regenerative braking units
In case the application needs it, be sure to use a specified type of braking resistor/regenerative
braking unit. In case of a braking resistor, install a thermal relay that monitors the temperature of
the resistor. Not doing so might result in a burn due to the heat generated in the braking resistor/
regenerative braking unit. Configure a sequence that enables the Inverter power to turn off when
unusual overheating is detected in the braking resistor/regenerative braking unit.
Electric protection of installation
Take safety precautions such as setting up a molded-case circuit breaker (MCCB) or fuses that
matches the Inverter capacity on the power supply side. Not doing so might result in damage to
property due to the short circuit of the load.
Wiring works and servicing the inverter
Wiring work must be carried out only by qualified personnel. Not doing so may result in a serious
injury due to an electric shock. Do not dismantle, repair or modify this product if you’re not autho-
rised and qualified for it. Doing so may result in an injury.
DC-link residual voltage
After switching off the mains supply, dangerous voltage can still be present in the VSD. When
opening the VSD for installing and/or commissioning activities wait at least 10 minutes. In case
of malfunction a qualified technician should check the DC-link or wait for one hour before dis-
mantling the VSD for repair.
Opening the variable speed drive cover
Only qualified technician can open the inverter. Always take adequate precautions before open-
ing the inverter. Although the connections for the control signals and the switches are isolated
from the main voltage, do not touch the control board when the variable speed drive is switched
on.
Do not manipulate inverter under power
Do not change wiring , put on or take off optional devices or replace cooling fans while the input
power is being supplied. Doing so may result in a serious injury due to an electric shock. Inspec-
tion of the Inverter must be conducted after the power supply has been turned off. Not doing so
may result in a serious injury due to an electric shock. The main power supply is not necessarily
shut off even if the emergency shutoff function is activated.
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...