78
Parameter sets
Section 10-2
Fig. 61 Mounting frame for the control panel
10-2 Parameter sets
Communication information for the different parameter sets.
The different parameter sets in the VSD have the following DeviceNet
instance numbers, Profibus slot/index numbers and EtherCAT index numbers:
Parameter set A contains parameters 43001 to 43556. The parameter sets B,
C and D contains the same type of information. For example parameter 43123
in parameter set A contain the same type of information as 44123 in parame-
ter set B.
A DeviceNet instance number can easily be converted into a Profibus slot/
index number or an EtherCAT index number according to description in sec-
tion section 11-8-2, page 254.
10-3 Motor data
Communication information for the different motors.
M1 contains parameters 43041 to 43048. The M2, M3, and M4 contains the
same type of information. For example parameter 43043 in motor M1 contain
the same type of information as 44043 in M2.
A DeviceNet instance number can easily be converted into a Profibus slot/
index number or an EtherCAT index number according to description in sec-
tion section 11-8-2, page 254.
Parameter
set
Modbus/DeviceNet
Instance number
Profibus
Slot/Index
EtherCAT index
(hex)
A
43001–43556
168/160 to 170/205
4bb9-4de4
B
44001–44529
172/140 to 174/185
4fa1-51cc
C
45001–45529
176/120 to 178/165
5389-55b4
D
46001–46529
180/100 to 182/145
5771-599c
Motor
Modbus/DeviceNet
Instance number
Profibus
Slot/Index
EtherCAT index
(hex)
M1
43041–43048
168/200 to 168/207
4be1-4be8
M2
44041–44048
172/180 to 174/187
4fc9-4fd0
M3
45041–45048
176/160 to 176/167
53b1-53b8
M4
46041–46048
180/140 to 180/147
5799-57a0
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...